Sub topic 9
The power triangle
This chapter assumes you know RMS values, phasors, impedance, and the definitions of real power P (W), reactive power Q (var), and apparent power S (VA). It shows how the three fit into one right triangle and how to use that triangle to solve problems.
Why a triangle
Real power P and reactive power Q are 90° apart in the phasor picture. Real power is the part of the product of voltage and current that does work. Reactive power is the part that swings in and out of magnetic and electric fields. Because the two components are perpendicular, they add like the sides of a right triangle, and apparent power S is the hypotenuse.
The angle between P and S is φ, the angle by which current lags or leads voltage.
The relationships
Draw P as the horizontal side, Q as the vertical side, and S as the hypotenuse. Then:
| Quantity | Formula |
|---|---|
| Apparent power | S = √(P² + Q²) = V I (RMS values) |
| Real power | P = S cos φ |
| Reactive power | Q = S sin φ |
| Power factor | pf = P / S = cos φ |
| Angle | φ = arctan(Q / P) |
Knowing any two of P, Q, S, and pf is enough to find the rest.
Worked example
Take the load from the earlier chapters: a 230 V RMS source driving 10 Ω of resistance in series with 10 Ω of inductive reactance. The impedance is 10 + j10 Ω, so |Z| = 14.14 Ω and I = 230 / 14.14 = 16.26 A.
- S = V I = 230 × 16.26 ≈ 3741 VA.
- φ = arctan(10 / 10) = 45°.
- P = S cos 45° ≈ 2645 W.
- Q = S sin 45° ≈ 2645 var.
Check with the Pythagorean relation: √(2645² + 2645²) ≈ 3741 VA. This matches.
Now suppose you only know P and pf. This script rebuilds the rest of the triangle:
import math
P = 2645.0 # W, real power
pf = 0.7071 # power factor
S = P / pf # apparent power in VA
Q = math.sqrt(S**2 - P**2) # reactive power magnitude in var
phi = math.degrees(math.acos(pf))
print(f"S = {S:.0f} VA")
print(f"Q = {Q:.0f} var")
print(f"phi = {phi:.1f} degrees")It prints S = 3741 VA, Q = 2645 var, and φ = 45.0°.
Common errors
- Adding S values directly. Apparent powers of separate loads do not add arithmetically unless their angles are equal. Add the P values and the Q values separately, then form the new S from those totals.
- Mixing peak and RMS values. S = V I only gives VA when both V and I are RMS. Using peak values doubles the result.
- Taking pf from the wrong angle. φ is the angle between voltage and current, not the angle of the current alone.
- Treating pf as a percentage of efficiency. A pf of 0.71 means 71% of the apparent power is real power. It does not mean 29% of the energy is lost.
Exercise
A lagging load draws 5 kW at a power factor of 0.8. Find the apparent power S and the reactive power Q.
Show answer
S = P / pf = 5000 / 0.8 = 6250 VA. Since cos φ = 0.8, sin φ = 0.6, so Q = S sin φ = 6250 × 0.6 = 3750 var, inductive because the load is lagging. Check: √(5000² + 3750²) = 6250 VA.