Sub topic 15
Distorted waveforms: displacement vs true power factor
This chapter assumes you know RMS values, real power P = V I cos φ, and the power triangle from the earlier chapters. It also assumes you can do basic sums with square roots.
Why one power factor is not enough
So far the voltage and current were pure sine waves at one frequency. Many modern loads, such as rectifiers, switching supplies, and LED drivers, draw current in short pulses. That current is not a sine wave. It can be written as a fundamental sine plus harmonics, which are sine waves at whole-number multiples of the supply frequency (150 Hz and 250 Hz on a 50 Hz supply).
Only components of the same frequency produce average power. If the supply voltage is a clean sine, the harmonic currents carry no real power. They still add to the RMS current, so they heat the wiring and load the source.
Two parts of the true power factor
The true power factor is the ratio of real power to apparent power: PF = P / (Vrms Irms). With a sinusoidal voltage it splits into two factors.
| Quantity | Formula | Meaning |
|---|---|---|
| Displacement power factor (DPF) | cos φ₁ | Phase shift between the fundamental voltage and fundamental current |
| Distortion factor | I₁ / Irms | Share of the RMS current that is the fundamental |
| True power factor | DPF × distortion factor | P / S for the whole waveform |
The total RMS current combines the harmonics as the square root of the sum of squares:
Irms = √(I₁² + I₃² + I₅² + …)
The total harmonic distortion of the current is THD = √(Irms² − I₁²) / I₁. The distortion factor can then be written as 1 / √(1 + THD²).
Worked example
A load on a 230 V sinusoidal supply draws a 10 A fundamental lagging by 30°, plus a 4 A third harmonic and a 3 A fifth harmonic.
import math
V = 230.0 # V RMS, pure sine
I1, phi1_deg = 10.0, 30.0 # fundamental current (A RMS) and lag angle
harmonics = [4.0, 3.0] # RMS currents of the 3rd and 5th harmonics
I_rms = math.sqrt(I1**2 + sum(h**2 for h in harmonics))
P = V * I1 * math.cos(math.radians(phi1_deg)) # only the fundamental does work
S = V * I_rms
dpf = math.cos(math.radians(phi1_deg))
dist = I1 / I_rms
thd = math.sqrt(I_rms**2 - I1**2) / I1
print(f"Irms = {I_rms:.2f} A, THD = {thd:.1%}")
print(f"P = {P:.0f} W, S = {S:.0f} VA")
print(f"DPF = {dpf:.4f}, distortion factor = {dist:.4f}")
print(f"true PF = P/S = {P / S:.4f}, DPF x distortion = {dpf * dist:.4f}")The two ways of computing true PF agree at about 0.775. The DPF alone is 0.866, so reading only the phase angle overstates how well the load uses the supply.
Common errors
- Quoting cos φ as the power factor for a distorted load. The result ignores the harmonic current and is too high.
- Including harmonic terms in P. With a sinusoidal supply voltage, they contribute zero average power.
- Expecting S² = P² + Q² to hold. With distortion, S² = P² + Q² + D², where D is the distortion power, in VA. The triangle becomes three-dimensional.
- Correcting with a capacitor and expecting a full fix.
Exercise
Exercise
A load on a sinusoidal supply has a displacement power factor of 0.90 and a current THD of 40%. What is the true power factor?
Show answer
The distortion factor is 1 / √(1 + 0.4²) = 1 / √1.16 ≈ 0.928. The true power factor is 0.90 × 0.928 ≈ 0.836.