Sub topic 10
Power factor and why utilities care
This chapter assumes you can compute RMS values, work with phasors and impedance, and know that real power P is in watts, reactive power Q is in var, and apparent power S is in VA, with S² = P² + Q². Here we define power factor and show why it affects cost and wiring.
What power factor is
Power factor (pf) is the ratio of real power to apparent power:
pf = P / S = cos(φ)
Here φ is the angle between the voltage and current phasors. For sinusoidal waveforms, pf runs from 0 to 1. A pf of 1 means all the current does useful work. A pf of 0.5 means only half of the VA delivered becomes real power.
Why current rises when pf falls
For a fixed real power P at voltage V, the current is:
I = P / (V · pf)
Halving the pf doubles the current. That extra current does no work, but it still heats every conductor and transformer it passes through.
The table below uses a load of 2645 W on a 230 V supply.
| Power factor | Current (A) | Apparent power (VA) |
|---|---|---|
| 1.00 | 11.50 | 2645 |
| 0.95 | 12.10 | 2784 |
| 0.7071 | 16.26 | 3741 |
| 0.50 | 23.00 | 5290 |
Going from pf 1.00 to 0.7071 raises the current by about 41 percent for exactly the same useful work.
Why utilities care
Utility equipment is rated in VA (or kVA), not watts. A transformer, cable, or generator is limited by the current it can carry and the voltage it can withstand. At a low pf, the equipment reaches its rating while delivering fewer watts.
- Conductor loss is I²R. A load at pf 0.7071 produces twice the I²R loss of the same load at pf 1.
- Voltage drop along the line grows with current.
- Transformers and generators must be larger for the same real power.
Utilities sell energy in kWh, which measures only real power. Because low pf costs them capacity and losses, many tariffs add a charge to industrial customers whose pf falls below a threshold, often around 0.9 to 0.95.
Worked example
The load from the earlier series R-L example has Z = 10 + j10 Ω on 230 V.
import math
V = 230.0
R, X = 10.0, 10.0
Z = math.hypot(R, X)
I = V / Z
phi = math.atan2(X, R)
pf = math.cos(phi)
P = V * I * pf
S = V * I
print(f"I = {I:.2f} A, P = {P:.0f} W, S = {S:.0f} VA, pf = {pf:.4f}")
print(f"Loss at pf=1 vs actual (same P): {1 / pf**2:.2f}x I^2R")The output shows I ≈ 16.26 A, P ≈ 2645 W, S ≈ 3741 VA, and pf ≈ 0.7071. The last line shows that the line carries twice the I²R loss it would at unity pf.
Exercise
A 400 V single-phase load draws 25 A and consumes 8 kW. What are its apparent power and power factor? What current would it draw at pf = 1?
Show answer
S = V·I = 400 × 25 = 10 000 VA. pf = P/S = 8000/10 000 = 0.80. At pf = 1, I = P/V = 8000/400 = 20 A, so the load draws 5 A less.