Sub topic 13
Correcting Power Factor with a Shunt Capacitor
This chapter assumes you know the power triangle, that inductive loads have a lagging power factor, and that a capacitor supplies reactive power. Here you will size a capacitor for a target power factor.
Why correct the power factor
The load from earlier chapters is a 230 V RMS source driving a series R-L load with R = 10 Ω and XL = 10 Ω. It draws P = 2645 W at a power factor of 0.7071 lagging. Its apparent power is about 3741 VA, so the current is about 16.26 A.
A load with a power factor of 0.95 would need only about 12.1 A for the same 2645 W. The wiring, transformers, and source see the full current, not just the part that does work. Correction lowers the current without changing the useful power.
The idea: cancel Q locally
An inductor takes reactive power from the source. A capacitor supplies it. Connecting a capacitor in parallel (shunt) with the load lets the two exchange reactive energy with each other instead of with the source.
The capacitor draws current that leads the voltage by 90°. This cancels part of the load's lagging reactive current. The load's real power is unchanged, because an ideal capacitor consumes no real power. Its voltage is also unchanged, because it sits across the same source.
The sizing procedure
- Compute the old reactive power: Qold = P tan(θold), where θold = arccos(pfold).
- Compute the target reactive power: Qnew = P tan(θnew), where θnew = arccos(pfnew).
- The capacitor must supply the difference: Qc = Qold − Qnew.
- A capacitor across voltage V has Qc = ωC V², so C = Qc / (2πf V²).
Use the RMS voltage in step 4. Use the voltage across the capacitor, which is the source voltage here.
For this load, tan(arccos 0.95) ≈ 0.3287, so Q_new ≈ 869 var. Then Qc = 2645 − 869 ≈ 1776 var. At 230 V and 50 Hz, C = 1776 / (314.16 × 52 900) ≈ 107 µF.
import math
P = 2645.0 # W, real power of the load
V = 230.0 # V RMS
f = 50.0 # Hz
pf_old = 0.7071
pf_new = 0.95
Q_old = P * math.tan(math.acos(pf_old))
Q_new = P * math.tan(math.acos(pf_new))
Q_c = Q_old - Q_new # reactive power the capacitor must supply
C = Q_c / (2 * math.pi * f * V**2) # shunt capacitor in farads
print(f"Qc = {Q_c:.0f} var")
print(f"C = {C * 1e6:.0f} microfarads")The script prints about 1776 var and 107 µF.
Check the result
After correction, S = P / 0.95 ≈ 2784 VA. The line current is 2784 / 230 ≈ 12.1 A, down from 16.26 A. Line losses scale with I², so they fall to about (12.1 / 16.26)² ≈ 0.55 of the old value, a reduction of about 45%.
Common errors
- Using P tan(θ) with degrees in a calculator set to radians, or the reverse.
- Using the apparent power S instead of P when computing Q.
- Correcting all the way to a leading power factor. Over-correction makes the line current rise again and can raise the voltage.
- Using the peak voltage in Qc = ωC V². The formula needs the RMS voltage.
Exercise
Exercise
A 230 V, 50 Hz load draws P = 2000 W at a power factor of 0.8 lagging. Find the shunt capacitance that raises the power factor to 1.0.
Show answer
At pf 0.8, tan(arccos 0.8) = 0.75, so Qold = 2000 × 0.75 = 1500 var. Unity power factor means Qnew = 0, so Qc = 1500 var. Then C = 1500 / (2π × 50 × 230²) = 1500 / 16 619 011 ≈ 9.03 × 10⁻⁵ F, or about 90 µF.