Sub topic 12
Complex power S = V I* from phasors
This chapter assumes you can multiply and divide complex numbers in polar and rectangular form. It also assumes you know phasors and impedance from the earlier chapters.
Why use complex power
The power triangle gives P, Q, and S with trigonometry. Complex power does the same job with one multiplication. It also keeps the sign of Q, so you can tell inductive loads from capacitive ones without extra reasoning.
The definition
Take RMS phasors V = V∠θv and I = I∠θi. The complex power is:
S = V I*
The asterisk means complex conjugate: keep the magnitude and flip the sign of the angle. The result is:
S = V I ∠(θv − θi) = V I cos φ + j V I sin φ
Here φ = θv − θi is the angle by which voltage leads current. So:
- Real part: P = V I cos φ, in watts.
- Imaginary part: Q = V I sin φ, in var.
- Magnitude: |S| = V I, in VA.
Sign of Q
With S = V I*, the sign of Q tells you the load type.
| Load | φ = θv − θi | Q | Power factor |
|---|---|---|---|
| Inductive (R-L) | positive | positive | lagging |
| Resistive | zero | zero | unity |
| Capacitive (R-C) | negative | negative | leading |
How the calculation flows
Worked example
A 230 V RMS source drives a series load of R = 10 Ω and XL = 10 Ω. Use the voltage as the 0° reference.
- Z = 10 + j10 Ω, which is 14.14∠45° Ω.
- I = V / Z = 230∠0° / 14.14∠45° = 16.26∠−45° A, which is 11.5 − j11.5 A.
- I* = 11.5 + j11.5 A.
- S = 230 × (11.5 + j11.5) = 2645 + j2645 VA.
So P = 2645 W, Q = 2645 var, and |S| = 3741 VA. The power factor is cos 45° = 0.7071. It is lagging because Q is positive.
You can check P another way. I² R = 16.263² × 10 = 2645 W, which matches the real part of S.
The same calculation in Python
import cmath
import math
V = 230 + 0j # RMS voltage phasor, reference at 0 degrees
Z = 10 + 10j # series R = 10 ohm, XL = 10 ohm
I = V / Z # RMS current phasor
S = V * I.conjugate() # complex power
P = S.real # real power in W
Q = S.imag # reactive power in var (positive = inductive)
S_mag = abs(S) # apparent power in VA
pf = P / S_mag
print(f"I = {abs(I):.2f} A")
print(f"P = {P:.0f} W, Q = {Q:.0f} var, S = {S_mag:.0f} VA")
print(f"pf = {pf:.4f} {'lagging' if Q > 0 else 'leading'}")
print(f"angle = {math.degrees(cmath.phase(S)):.1f} degrees")Expected output:
I = 16.26 A
P = 2645 W, Q = 2645 var, S = 3741 VA
pf = 0.7071 lagging
angle = 45.0 degreesCommon errors
- Forgetting the conjugate. Then S = V I has angle θv + θi, which means nothing physical.
- Mixing peak and RMS phasors in the same calculation.
- Reading the sign of Q from the current angle alone. Always compare it with the voltage angle.
- Adding apparent powers as magnitudes. Add complex powers instead. Total P and total Q add across loads, but total |S| does not.
Exercise
A load has V = 120∠0° V RMS and draws I = 10∠30° A RMS. Find S, P, Q, and the power factor. State whether the power factor is lagging or leading.
Show answer
I* = 10∠−30° A, so S = 120 × 10 ∠(0° − 30°) = 1200∠−30° VA. In rectangular form, P = 1200 cos(−30°) = 1039 W and Q = 1200 sin(−30°) = −600 var. The power factor is cos 30° = 0.866. Q is negative and the current leads the voltage, so the power factor is leading and the load is capacitive.