Sub topic 8
Apparent power: what the source and wiring must carry
This chapter assumes you can compute RMS values, read a phasor angle, and find the impedance of a series R-L load. It builds on real power P and reactive power Q from the previous two chapters.
What apparent power is
Apparent power S is the product of the RMS voltage and the RMS current:
S = Vrms × Irms
Its unit is the volt-ampere (VA). It is not measured in watts, because it is not the average power that does work. It tells you how much voltage and current the source, cables, and protective devices must handle.
A wire heats up according to the current through it, whatever the phase angle. A transformer's insulation is limited by voltage, and its windings are limited by current. So equipment is rated in VA or kVA, not in watts.
How S relates to P and Q
Real power is P = Vrms Irms cos φ. Reactive power is Q = Vrms Irms sin φ. Squaring and adding them gives:
S² = P² + Q², so S = √(P² + Q²)
P and Q are at right angles in the power triangle, and S is the hypotenuse. S is always at least as large as P. They are equal only when φ = 0, which is a purely resistive load.
Do not add S values arithmetically as if they were in phase. Add the P values and the Q values separately, then combine them.
Worked example
A 230 V RMS source drives a series load with R = 10 Ω and XL = 10 Ω.
- Impedance magnitude: |Z| = √(10² + 10²) ≈ 14.14 Ω.
- Current: Irms = 230 / 14.14 ≈ 16.26 A.
- Apparent power: S = 230 × 16.26 ≈ 3741 VA.
- Real power: P = Irms² R = 16.26² × 10 ≈ 2645 W.
- Reactive power: Q = Irms² XL ≈ 2645 var.
Check the triangle: √(2645² + 2645²) ≈ 3741 VA. The source supplies 3741 VA of capability, but only 2645 W does work. The ratio P/S is 0.7071, which is the power factor.
import math
V = 230.0
R = 10.0
XL = 10.0
Z = math.hypot(R, XL)
I = V / Z
S = V * I
P = I**2 * R
Q = I**2 * XL
print(f"I = {I:.2f} A")
print(f"S = {S:.0f} VA")
print(f"P = {P:.0f} W, Q = {Q:.0f} var")
print(f"sqrt(P^2 + Q^2) = {math.hypot(P, Q):.0f} VA")Why the wiring cares
The same 2645 W delivered to a purely resistive load at 230 V needs only 2645 / 230 ≈ 11.5 A. The inductive load needs 16.26 A, about 41% more. The cable loses power as I² Rcable, so the extra current raises the cable loss by a factor of (16.26 / 11.5)², which is about 2.
Common errors
- Calling S "watts". Use VA so that readers know it is not real power.
- Computing S as P + Q. The correct sum is a vector (square-root) sum.
- Sizing a generator or transformer from watts alone. Size it from VA.
- Assuming a meter reading in VA equals the energy you are billed for. Residential billing usually counts watt-hours, though many industrial tariffs also charge for kVA demand or poor power factor.
Exercise
A 120 V RMS load draws 10 A at a power factor of 0.8 lagging. Find S, P, and Q.
Show answer
S = 120 × 10 = 1200 VA. P = S × pf = 1200 × 0.8 = 960 W. Q = √(S² − P²) = √(1200² − 960²) = 720 var, and it is positive (inductive) because the power factor is lagging.
Exercise
A 5 kVA generator supplies a load with a power factor of 0.6. What is the most real power it can deliver without overload?
Show answer
P = S × pf = 5000 × 0.6 = 3000 W, or 3 kW. The generator reaches its current limit at 3 kW, so raising the power factor would let it supply more real power.