Sub topic 11
Lagging and Leading Power Factor: Inductive vs Capacitive Loads
This chapter assumes you know phasors, impedance of R, L, and C, and the power triangle from the earlier chapters. Power factor (pf) is the ratio P/S, so it is a number between 0 and 1. That number does not say whether the current is behind or ahead of the voltage. The words "lagging" and "leading" supply that missing information.
The convention
Power factor is named from the current's point of view, with the voltage phasor as the reference.
- Lagging pf: the current lags the voltage. The load is inductive and absorbs reactive power, so Q > 0.
- Leading pf: the current leads the voltage. The load is capacitive and supplies reactive power, so Q < 0.
With the phase angle φ = θv − θi, the real power is P = Vrms Irms cos φ and the reactive power is Q = Vrms Irms sin φ. The sign of φ gives the sign of Q. Because cos φ is the same for +φ and −φ, the pf value alone cannot tell the two cases apart. That is why you always write "0.71 lagging" or "0.71 leading".
| Load type | Impedance angle φ | Current relative to voltage | Sign of Q | Power factor |
|---|---|---|---|---|
| Resistive | 0° | In phase | 0 | 1 (unity) |
| Inductive (R-L) | 0° to +90° | Lags | Positive | Lagging |
| Capacitive (R-C) | 0° to −90° | Leads | Negative | Leading |
A memory aid is ELI the ICE man. In an inductor (L), voltage (E) leads current (I). In a capacitor (C), current (I) leads voltage (E).
Worked example
Take a 230 V RMS source and compare two series loads. Both have R = 10 Ω, and the reactance magnitude is 10 Ω in each case.
For the R-L load, Z = 10 + j10 Ω = 14.14∠45° Ω. The current is I = 230 / (14.14∠45°) = 16.26∠−45° A, so it lags the voltage by 45°.
- S = Vrms Irms = 230 × 16.26 ≈ 3741 VA
- P = S cos 45° ≈ 2645 W
- Q = S sin 45° ≈ +2645 var
- pf = 0.7071 lagging
For the R-C load, Z = 10 − j10 Ω = 14.14∠−45° Ω. The current is 16.26∠+45° A, so it leads the voltage.
- P is still ≈ 2645 W
- Q ≈ −2645 var
- pf = 0.7071 leading
The magnitudes are identical. Only the sign of Q and the direction of the phase shift differ.
import cmath
import math
V = 230 + 0j # RMS voltage phasor, reference at 0 degrees
for name, Z in [("R-L", 10 + 10j), ("R-C", 10 - 10j)]:
I = V / Z
S = V * I.conjugate()
pf = S.real / abs(S)
kind = "lagging" if S.imag > 0 else "leading"
print(f"{name}: P = {S.real:.0f} W, Q = {S.imag:+.0f} var, "
f"pf = {pf:.4f} {kind}, "
f"current angle = {math.degrees(cmath.phase(I)):+.0f} deg")Running this prints Q = +2645 var for R-L and Q = −2645 var for R-C. The sign of S.imag decides the label.
Why the distinction matters
Most industrial loads are inductive. Motors, transformers, and fluorescent ballasts all have magnetic fields, so they present a lagging pf. A capacitor supplies the reactive power that an inductor absorbs. Placing a capacitor in parallel with an inductive load therefore cancels some of the load's Q, and the source then delivers less reactive current. This is the basis of power factor correction, covered in a later chapter.
Common errors
- Reporting only the number. "pf = 0.8" is incomplete. State lagging or leading.
- Mixing up the sign convention. Q from S = V I is positive for inductive loads. If you compute S = V I, the sign flips.
- Overcorrecting. Adding too much capacitance turns a lagging load into a leading one. The pf magnitude can then fall again even though capacitors were added.
- Reading φ from the wrong reference. The angle φ is voltage angle minus current angle, not the reverse.
Exercise
A load draws 8 kW at 400 V RMS with a current that leads the voltage. The power factor is 0.8. Find S and Q, and state the sign of Q.
Show answer
S = P / pf = 8000 / 0.8 = 10 000 VA. sin φ = √(1 − 0.8²) = 0.6, so |Q| = S × 0.6 = 6000 var. The current leads, so the pf is leading and Q = −6000 var. The load is capacitive and supplies reactive power.