Sub topic 14
Power in balanced three-phase systems
This chapter assumes you know real, reactive, and apparent power, the power triangle, and phasors. It extends them to balanced three-phase circuits, the form in which most industrial power is delivered.
What "balanced" means
A three-phase source has three voltages of equal magnitude, each shifted 120° from the next. A load is balanced when all three phases have the same impedance. Then the three line currents also have equal magnitude and are 120° apart.
In a balanced system, the instantaneous powers of the three phases add to a constant. Total power does not pulse at twice the line frequency as it does in a single-phase circuit. That smooth delivery is one reason three-phase motors run with less vibration.
Wye and delta relationships
Loads connect in one of two ways. In a wye (Y) connection, each load sits between a line and the neutral point. In a delta (Δ) connection, each load sits between two lines.
| Connection | Line voltage V_L | Line current I_L |
|---|---|---|
| Wye | √3 × V_phase | I_phase |
| Delta | V_phase | √3 × I_phase |
VL is the voltage between two lines. IL is the current in one line conductor.
Total power from per-phase power
Each phase obeys the single-phase rules. If Vph and Iph are RMS values and φ is the angle between them, one phase has P = Vph Iph cos φ. The balanced total is three times that.
Substituting the table relationships gives the same result for wye and delta. Written with line values, it is:
- Real power: P = √3 · VL · IL · cos φ
- Reactive power: Q = √3 · VL · IL · sin φ
- Apparent power: S = √3 · VL · IL
The power triangle still holds, with S² = P² + Q² and pf = P / S = cos φ.
Worked example
A balanced motor load draws 10 A per line from a 400 V line-to-line supply. Its power factor is 0.8 lagging.
import math
V_LL = 400.0 # line-to-line RMS voltage, volts
I_L = 10.0 # line current, amperes
pf = 0.8 # lagging
S = math.sqrt(3) * V_LL * I_L
P = S * pf
Q = S * math.sqrt(1 - pf**2) # positive for a lagging (inductive) load
print(f"S = {S:.0f} VA")
print(f"P = {P:.0f} W")
print(f"Q = {Q:.0f} var")The output is S = 6928 VA, P = 5543 W, and Q = 4157 var.
As a check, a wye connection has a phase voltage of 400 / √3 ≈ 230.9 V and a phase current of 10 A. One phase has S = 2309 VA, and three phases give 6928 VA.
Why it matters for power factor
Power factor correction works on three-phase loads as it does on single-phase ones. Compute the total Q to remove, then split it equally over three capacitors, one per phase. The saved current also reduces conductor losses, which are proportional to I² in all three lines.
Three-phase delivery also saves copper. A three-phase line carries the same power as a single-phase line at the same voltage and power factor, using less conductor material overall.
Common errors
- Using phase voltage in a formula written for line voltage, or the reverse. This gives an error of exactly √3.
- Forgetting that √3 appears only in the line-value formulas. With per-phase values, multiply by 3 instead.
- Applying these formulas to an unbalanced load. Then each phase must be calculated separately and the complex powers added.
Exercise
A balanced three-phase load is supplied at 415 V line-to-line and draws 20 A per line at a power factor of 0.9 lagging. Find S, P, and Q.
Show answer
S = √3 × 415 × 20 ≈ 14,376 VA. P = S × 0.9 ≈ 12,938 W. Q = S × √(1 − 0.9²) = S × 0.4359 ≈ 6,266 var, inductive because the power factor is lagging.