Sub topic 6
Real power: the average that does work
This chapter derives real power from the instantaneous power p(t). It then shows what each load type does to that average and how to compute and check it. It assumes you know RMS values, phasors, and impedance from earlier chapters. It also assumes you can use trigonometric product identities and that you know how R, L, and C relate voltage to current.
Starting point: the product v(t) i(t)
Take a load with a sinusoidal voltage and a current that lags it by the angle φ:
- v(t) = Vm sin(ωt)
- i(t) = Im sin(ωt − φ)
Here Vm and Im are peak values. Instantaneous power is their product, in watts at every instant:
p(t) = v(t) i(t) = Vm Im sin(ωt) sin(ωt − φ)
Use the identity sin A sin B = ½[cos(A − B) − cos(A + B)] with A = ωt and B = ωt − φ. Then A − B = φ and A + B = 2ωt − φ, so:
p(t) = (Vm Im / 2) cos φ − (Vm Im / 2) cos(2ωt − φ)
The result has two parts:
- A constant term, (Vm Im / 2) cos φ, which does not change with time.
- A sinusoid at twice the supply frequency, with amplitude Vm Im / 2 and zero average.
Power oscillates at 2ω because both v and i change sign every half cycle. Each sign change in one is matched by a change in the other, so the product repeats twice per voltage cycle.
Averaging over one period
Real power P, also called active power, is the average of p(t) over one full period T:
P = (1/T) ∫₀ᵀ p(t) dt
The 2ω term completes exactly two full cycles in T, so it integrates to zero. Only the constant term remains:
P = (Vm Im / 2) cos φ
Peak values relate to RMS values by Vm = √2 Vrms and Im = √2 Irms. Substituting gives the central formula of this chapter:
P = Vrms Irms cos φ
The unit is the watt (W). The factor cos φ is the power factor, which a later chapter treats in full. For now, read it as the fraction of the volt-ampere product that turns into average power.
What the formula says for each load type
The angle φ is the angle of the load impedance. Positive φ means the current lags the voltage.
| Load | φ | cos φ | Real power P | Behavior of p(t) |
|---|---|---|---|---|
| Pure resistor | 0° | 1 | Vrms Irms = Irms² R | Never negative |
| Pure inductor | +90° | 0 | 0 | Swings equally positive and negative |
| Pure capacitor | −90° | 0 | 0 | Swings equally positive and negative |
| Series R-L | 0° to 90° | between 0 and 1 | Irms² R | Negative for part of each cycle |
| Series R-C | −90° to 0° | between 0 and 1 | Irms² R | Negative for part of each cycle |
A pure inductor or capacitor has φ = ±90°, so the constant term vanishes. All the power it takes in during one part of the cycle returns to the source in the next part. It dissipates nothing. A later chapter calls that back-and-forth flow reactive power.
For a load with both resistance and reactance, only the resistance consumes real power. This gives two equivalent forms that avoid the angle:
- P = Irms² R, where R is the resistive part of the impedance.
- P = Vrms² / R for a purely resistive load.
The first form holds for any series R-L-C load. The second does not. For a series R-L load, the voltage across the whole load is not the voltage across R, so Vrms² / R would give the wrong answer. Use Irms² R, or use the voltage across R alone.
Why instantaneous power goes negative
When φ is not zero, p(t) is negative during part of each cycle. Voltage and current then have opposite signs, so energy flows from the load back to the source. The size of that interval grows with |φ|. At φ = 0 the interval is zero, and at φ = 90° the positive and negative lobes are equal, which makes the average zero.
The average power is the net energy flow. Energy that goes out and comes back cancels, and only the net energy delivered to the load remains. That net energy is what becomes heat, mechanical work, light, or chemical change.
A numerical check
The following program checks the derivation numerically. It samples v(t) i(t) over exactly one period and averages the samples. The load is the series R-L circuit from earlier chapters, with R = 10 Ω and XL = 10 Ω on a 230 V, 50 Hz supply. Its current is 230 / (10√2) ≈ 16.263 A, lagging by 45°.
import math
Vrms = 230.0
Irms = 16.263 # amperes
phi = math.radians(45) # current lags voltage by 45 degrees
f = 50.0
N = 1000 # samples over exactly one period
p_sum = 0.0
for n in range(N):
t = n / (N * f)
v = math.sqrt(2) * Vrms * math.sin(2 * math.pi * f * t)
i = math.sqrt(2) * Irms * math.sin(2 * math.pi * f * t - phi)
p_sum += v * i
P_avg = p_sum / N
print(f"average of v*i = {P_avg:.0f} W")
print(f"Vrms*Irms*cos(phi) = {Vrms * Irms * math.cos(phi):.0f} W")Both lines print 2645 W. Two other calculations agree with that value. Irms² R = 16.263² × 10 ≈ 2645 W. The complex power calculation S = V I* gives a real part of 2645 W.
Two details keep the numerical average accurate:
- The samples cover exactly one period (N points spaced T/N apart, with the last one before t = T). Averaging over a fractional number of cycles leaves part of the 2ω term in the result.
- Evenly spaced samples of a sinusoid averaged over a whole period cancel the 2ω term exactly, apart from floating-point rounding.
Sign conventions and direction
Real power has a sign that depends on the reference direction. With the passive sign convention, current enters the positive voltage terminal. Positive P then means the element absorbs power on average, and negative P means it delivers power on average. For a passive network made only of R, L, and C, P is never negative, because |φ| ≤ 90°. Negative P appears with a generator, a regenerating motor, or a grid-tied inverter exporting energy.
Where the formula stops applying
The derivation assumed pure sinusoids at one frequency. Three situations need care:
- A DC offset. If v or i has a DC component, the product contains an extra constant term, Vdc Idc. Real power is then the sum of the DC power and the AC power.
- Harmonics. With non-sinusoidal waveforms, the definition P = (1/T) ∫ v i dt still holds. The shortcut Vrms Irms cos φ does not. Only harmonics present in both voltage and current contribute, each with its own angle, and total real power is the sum of those contributions. The last chapter of this tutorial covers this.
- Different frequencies. Voltage and current components at different frequencies produce products that average to zero over a common period. They do not add real power.
The averaging definition is the general one. When you are unsure, return to it.
Measuring real power
A wattmeter multiplies instantaneous voltage and current and low-pass filters the result. That is the same operation as the average above. A digital power meter samples v and i, multiplies them point by point, and averages over an integer number of cycles, like the program in this chapter. This gives the correct real power for distorted waveforms. A meter that measures only Vrms and Irms separately and multiplies them reports apparent power instead.
Common mistakes
- Using cos φ with the wrong angle. φ is the angle between voltage and current, equal to the impedance angle. It is not the angle of the voltage or current against an arbitrary reference.
- Using the voltage across the whole load with only R. Use Irms² R, or the voltage across R alone.
- Expecting a reactive element to dissipate power. An ideal inductor or capacitor has P = 0. In a real component, the small loss comes from its winding or dielectric resistance, which is a resistive effect.
- Mixing peak and RMS. The formula P = Vrms Irms cos φ takes RMS values. With peak values, the formula is P = ½ Vm Im cos φ.
Exercise
A load connected to a 120 V RMS supply draws 10 A RMS, and the current lags the voltage by 60°. (a) What is the real power? (b) If the load is a series R-L circuit, what is its resistance R?
Show answer
(a) P = Vrms Irms cos φ = 120 × 10 × cos 60° = 120 × 10 × 0.5 = 600 W. (b) All real power is dissipated in R, so P = Irms² R. Then R = 600 / 10² = 6 Ω. As a check, the impedance magnitude is 120 / 10 = 12 Ω and R = |Z| cos 60° = 6 Ω.
Exercise
A voltage v(t) = 325 sin(314t) V is applied to a load, and the current is i(t) = 14.1 sin(314t + 30°) A. Find the real power, and say whether the load is inductive or capacitive.
Show answer
Peak values give Vrms = 325 / √2 ≈ 230 V and Irms = 14.1 / √2 ≈ 10 A. The current leads the voltage by 30°, so φ = −30° and cos φ = 0.866. P = 230 × 10 × 0.866 ≈ 1992 W, about 2.0 kW. A leading current means the load is capacitive. The cosine is even, so the sign of φ does not change P. It does change the sign of reactive power, which later chapters cover.