Sub topic 8
Apparent power: what the source and wiring must carry
This chapter assumes you can already compute RMS values, express voltage and current as phasors, and calculate real power P and reactive power Q for a load. It uses P in watts (W) and Q in volt-amperes reactive (var). Here you add apparent power, the quantity that determines how much current a source, cable, or transformer must carry.
Definition
Apparent power S is the product of the RMS voltage and the RMS current:
S = Vrms × Irms
Its unit is the volt-ampere (VA). Use VA, not W, so that apparent power is not confused with real power. Nothing in this product accounts for the phase angle between voltage and current. S is the largest real power the load could consume at that voltage and current, and that happens only when the two are in phase.
A load with real power P and reactive power Q has apparent power:
S = √(P² + Q²)
Real power equals S cos φ, and reactive power equals S sin φ, where φ is the angle by which voltage leads current. This is the same relationship you will draw as the power triangle in the next chapter.
Worked example: a series R-L load
Take the 230 V RMS source driving a series load with R = 10 Ω and XL = 10 Ω.
- The impedance magnitude is |Z| = √(10² + 10²) = 14.142 Ω.
- The RMS current is I = 230 / 14.142 = 16.26 A.
- The apparent power is S = 230 × 16.26 ≈ 3741 VA.
- The real power is P = I²R = 16.26² × 10 ≈ 2645 W.
- The reactive power is Q = I²XL ≈ 2645 var.
Check: √(2645² + 2645²) = 2645 × 1.4142 ≈ 3741 VA. The power factor is P/S = 2645/3741 ≈ 0.7071, and the current lags the voltage by 45°.
The source delivers 16.26 A, but only 2645 W does useful work. The remaining capacity is spent carrying reactive current that swings energy into and out of the inductor.
import math
V = 230.0
R, XL = 10.0, 10.0
Z = math.hypot(R, XL)
I = V / Z
S = V * I
P = I**2 * R
Q = I**2 * XL
print(f"I = {I:.2f} A")
print(f"S = {S:.0f} VA")
print(f"P = {P:.0f} W, Q = {Q:.0f} var")
print(f"sqrt(P^2 + Q^2) = {math.hypot(P, Q):.0f} VA")The last line prints the same value as S. This confirms that S is the hypotenuse of P and Q, not their sum.
Why the source and wiring care about S
Cables, breakers, generators, and transformers are limited by current and voltage. Heating in a conductor depends on the RMS current through it, regardless of whether that current carries real or reactive power. The conductor loss is:
Ploss = I² Rwire
The meter on the load sees only P, but the wiring sees I, and I = S / V. For a fixed real power P, a lower power factor means a larger S and so a larger current.
The next script holds the real power fixed at 2645 W and varies the power factor.
V = 230.0
P = 2645.0
print("pf I (A) S (VA) relative wire loss")
for pf in (1.0, 0.95, 0.7071):
I = P / (V * pf)
S = V * I
loss = (I / (P / V)) ** 2
print(f"{pf:.4f} {I:6.2f} {S:8.0f} {loss:.2f}x")| Power factor | Current (A) | Apparent power (VA) | Wire loss relative to pf = 1 |
|---|---|---|---|
| 1.0000 | 11.50 | 2645 | 1.00× |
| 0.9500 | 12.10 | 2784 | 1.11× |
| 0.7071 | 16.26 | 3741 | 2.00× |
Wire loss scales with 1/pf². At a power factor of 0.7071 the same useful power costs twice the heating in the wiring. A cable sized for 11.5 A would be overloaded at 16.26 A, even though the load does no more work.
Equipment is rated in VA
Transformers, generators, and uninterruptible power supplies carry ratings in kVA, not kW. The manufacturer does not know the power factor of the load you will connect. Winding heating depends on current, and insulation depends on voltage, so the product of the two is the meaningful limit.
Example: a 5 kVA transformer at 230 V can carry at most 5000 / 230 ≈ 21.7 A. A load of 4 kW at power factor 0.7 needs:
S = 4000 / 0.7 ≈ 5714 VA
This exceeds the rating, even though 4 kW is below 5 kW. At a power factor of 0.7071, the largest real power the transformer can serve is:
P = 5000 × 0.7071 ≈ 3536 W
Apparent powers do not add
Real power adds arithmetically, and so does reactive power (with sign). Apparent power adds only when the loads have the same phase angle. Otherwise the magnitudes of the individual S values sum to more than the true total.
Example with two loads on the same source:
| Load | P (W) | Q (var) | S (VA) |
|---|---|---|---|
| A | 3000 | 4000 | 5000 |
| B | 4000 | 3000 | 5000 |
| Total | 7000 | 7000 | 9899 |
The total P is 3000 + 4000 = 7000 W, and the total Q is 4000 + 3000 = 7000 var. Then S = √(7000² + 7000²) ≈ 9899 VA, not 5000 + 5000 = 10 000 VA. The correct method is to add P and Q first, then take the magnitude.
import math
loads = [(3000.0, 4000.0), (4000.0, 3000.0)] # (P in W, Q in var)
P_total = sum(p for p, _ in loads)
Q_total = sum(q for _, q in loads)
S_total = math.hypot(P_total, Q_total)
S_naive = sum(math.hypot(p, q) for p, q in loads)
print(f"P = {P_total:.0f} W, Q = {Q_total:.0f} var")
print(f"S (correct) = {S_total:.0f} VA")
print(f"S (naive sum) = {S_naive:.0f} VA")If one load is capacitive, its Q is negative, so it reduces the total Q and therefore the total S. This is the basis of power factor correction, which a later chapter develops.
Common errors
- Multiplying RMS values and calling the result watts. Vrms × Irms gives VA. Multiply by cos φ to get W.
- Mixing peak and RMS. S uses RMS values. If you use peak values, the product is twice as large (Vpk Ipk = 2 Vrms Irms).
- Summing S values. Add P and Q, then compute S from the totals.
- Using the wrong unit label. Write VA for S, W for P, and var for Q. The dimensions are the same, but the labels tell the reader which quantity you mean.
- Assuming the wire sees only P. The wire carries the full RMS current. Conductor heating and voltage drop follow I, not P.
Summary
- Apparent power S = Vrms × Irms, in VA, is the quantity that sets the current the source and wiring carry.
- S = √(P² + Q²), P = S cos φ, and Q = S sin φ.
- At fixed P, conductor loss scales with 1/pf², so a power factor of 0.7071 doubles the wire loss.
- Transformers and generators are rated in kVA because heating depends on current, not on the load's phase angle.
- Combine loads by adding P and Q, not S.
Exercise
A single-phase 230 V load draws 20 A at a power factor of 0.8 lagging. (a) Find S, P, and Q. (b) A 5 kVA supply serves this load. Is it overloaded? (c) If the power factor were raised to 1.0 with the same real power, what current would the load draw?
Show answer
(a) S = 230 × 20 = 4600 VA. P = S × pf = 4600 × 0.8 = 3680 W. Q = √(4600² − 3680²) = √(21 160 000 − 13 542 400) = √7 617 600 ≈ 2760 var (inductive, since the power factor is lagging). (b) No. 4600 VA is below 5000 VA, and the current of 20 A is below the supply's limit of 5000 / 230 ≈ 21.7 A. (c) I = P / V = 3680 / 230 = 16.0 A. The current falls from 20 A to 16 A, and the wire loss falls by a factor of (16/20)² = 0.64.
Exercise
Load 1 draws P = 6 kW and Q = 8 kvar. Load 2 draws P = 8 kW and Q = −6 kvar (capacitive). Both are connected to the same 230 V source. Find the total S and the total current.
Show answer
Total P = 6 + 8 = 14 kW. Total Q = 8 + (−6) = 2 kvar. S = √(14² + 2²) = √200 ≈ 14.14 kVA. The current is I = 14 142 / 230 ≈ 61.5 A. Adding the individual S values (10 + 10 = 20 kVA) would overestimate the current as 87 A, because the capacitive load cancels part of the inductive reactive power.