Sub topic 13
Correcting power factor with a shunt capacitor
This chapter assumes you can compute real, reactive and apparent power from a power triangle, and that you know the capacitor current relation I = V/Xc. You should also be comfortable with complex numbers in rectangular form. The goal is to size a capacitor that raises a lagging power factor to a target value, and to understand what the correction does and does not change.
Why correct the power factor
Take the load from earlier in this tutorial: a 230 V RMS, 50 Hz source driving a series R = 10 Ω, XL = 10 Ω load. It draws 16.26 A and consumes 2645 W, but its apparent power is 3741 VA. The wiring, transformer and generator must carry all 16.26 A, even though only 70.71% of the apparent power does useful work.
The extra current is the reactive component. It swings energy into the load's magnetic field and back out again, twice per cycle. That current produces I²R heating in conductors and voltage drop along the feeder. It also uses up transformer capacity that could serve other customers. Utilities therefore often bill a penalty when a site's power factor falls below a threshold, commonly somewhere between 0.85 and 0.95.
Correction means supplying the reactive current locally, so it no longer has to come from the source.
The idea: cancel Q with an opposite Q
An inductive load has positive Q by convention. A capacitor has negative Q. It supplies reactive power in the same instants that the inductor demands it. Connecting a capacitor in parallel (shunt) with the load lets the two exchange energy with each other instead of with the source.
Two facts make the calculation simple:
- A shunt capacitor does not change the voltage across the load, so the load's real power P is unchanged.
- Reactive powers add algebraically, so the new net reactive power is Qnew = Qload − Q_c.
The sizing procedure
The derivation behind step E is short. A capacitor at RMS voltage V has current I = V/Xc = ωCV. Its reactive power magnitude is Q_c = V·I = ωCV². Solving for C gives:
C = Q_c / (2πf V²)
The tangent form in steps B and C comes from the power triangle. Since tan φ = Q/P, we have Q = P tan φ, and φ = acos(pf).
Worked example
Raise the 2645 W, 0.7071 lagging load to a power factor of 0.95 at 230 V and 50 Hz.
- Q_old = 2645 × tan(45°) ≈ 2645 var.
- Q_new = 2645 × tan(acos 0.95) = 2645 × 0.3287 ≈ 869 var.
- Q_c = 2645 − 869 ≈ 1776 var.
- C = 1776 / (2π × 50 × 230²) ≈ 107 µF.
The script below does the same arithmetic.
import math
P = 2645.0 # W, real power of the load
V = 230.0 # V RMS
f = 50.0 # Hz
pf_old = 0.7071
pf_new = 0.95
Q_old = P * math.tan(math.acos(pf_old))
Q_new = P * math.tan(math.acos(pf_new))
Q_c = Q_old - Q_new # reactive power the capacitor must supply
C = Q_c / (2 * math.pi * f * V**2) # shunt capacitor in farads
print(f"Qc = {Q_c:.0f} var")
print(f"C = {C * 1e6:.0f} microfarads")It prints about 1776 var and 107 microfarads. The spine rounds the reactive power to 1.78 kvar.
Verify the result with phasors
Never trust a sizing formula without a check. Parallel branches share one voltage, so currents add. Add the capacitor branch current to the load current and recompute complex power.
import cmath
import math
V = 230 + 0j
Z_load = 10 + 10j
f = 50.0
C = 107e-6
I_load = V / Z_load # 11.5 - 11.5j A
I_cap = V * 1j * 2 * math.pi * f * C # capacitor current leads V by 90 degrees
I_total = I_load + I_cap
S = V * I_total.conjugate()
pf = S.real / abs(S)
print(f"load current = {abs(I_load):.2f} A")
print(f"cap current = {abs(I_cap):.2f} A")
print(f"source current = {abs(I_total):.2f} A")
print(f"P = {S.real:.0f} W, Q = {S.imag:.0f} var, S = {abs(S):.0f} VA")
print(f"pf = {pf:.3f} {'lagging' if S.imag > 0 else 'leading'}")The capacitor current is about 7.73 A, pointing along the +j axis. It cancels most of the −11.5j component of the load current, leaving a source current of about 12.10 A. The real power stays at 2645 W, and the new power factor is about 0.95 lagging.
What changes and what does not
| Quantity | Before | After (C = 107 µF) |
|---|---|---|
| Real power P | 2645 W | 2645 W |
| Reactive power Q | 2645 var | about 869 var |
| Apparent power S | 3741 VA | about 2784 VA |
| Source current | 16.26 A | about 12.10 A |
| Power factor | 0.707 lagging | 0.95 lagging |
| Relative feeder I²R loss | 1.00 | about 0.55 |
The current drops by about 26%. Because feeder loss goes with the square of current, loss falls by about 45%. The load's own current, 16.26 A, is unchanged. Only the current in the feeder upstream of the capacitor drops.
Do not overcorrect
Qc must not exceed Qold, or the net reactive power becomes negative and the power factor turns leading. Full correction to unity needs Q_c = 2645 var, which gives C = 2645 / (2π × 50 × 230²) ≈ 159 µF. Past that value, the power factor falls again, now leading, and the current rises again.
Overcorrection has practical costs:
- Leading current can raise the voltage at the load end of a lightly loaded feeder (the Ferranti effect).
- Many tariffs penalize leading power factor as well.
- A load that varies, such as a motor that is often unloaded, can end up overcorrected whenever its Q drops while the capacitor stays connected.
Targets of 0.95 to 0.98 are common. Going all the way to 1.00 buys little, because the last few percent of power factor need a large amount of capacitance for a small drop in current.
Practical edge cases
Capacitor voltage rating. The formula uses the voltage actually across the capacitor. A capacitor labeled 1.8 kvar at 230 V delivers less at a lower voltage, in proportion to V². Choose the rating at the real operating voltage, and keep a safety margin for voltage rise.
Fixed versus switched banks. A fixed capacitor suits a load that is steady. For a plant whose Q varies, an automatic power factor controller switches capacitor steps in and out to track the load.
Motors. When a capacitor is wired across a motor and switched with it, keep the correction below the motor's no-load magnetizing reactive power. Larger values can cause self-excitation and overvoltage when the motor is switched off while still spinning.
Harmonics. A capacitor's reactance falls as frequency rises. In a plant with nonlinear loads, such as drives and rectifiers, the capacitor and the supply inductance can form a parallel resonance near a harmonic frequency. This resonance amplifies harmonic currents and can overheat or destroy the capacitor. Detuned reactors in series with the capacitor move that resonance below the lowest significant harmonic. A later chapter covers distortion power factor.
Series versus shunt. The capacitor must be in parallel with the load. A series capacitor changes the load's impedance and its voltage, and it does not leave the load's operation untouched.
Rounding. Standard capacitor values come in steps, so you pick the nearest available size. Recheck the resulting power factor after choosing it, as the second script does.
Sizing with a different load
The approach scales to any load. Given P and two power factors, only the tangent difference matters:
Qc = P (tan φold − tan φ_new)
Since the factor in parentheses depends only on the two power factors, you can tabulate it. A load at 0.80 lagging corrected to 0.95 needs 0.4263 kvar per kW, because tan(acos 0.80) = 0.75 and tan(acos 0.95) = 0.3287. Multiply by the real power in kW to get the kvar.
Exercise
A 10 kW load at 0.80 lagging runs from a 400 V, 50 Hz supply. Find the capacitor, in microfarads, that raises its power factor to 0.95 lagging. Treat the capacitor as a single shunt unit across the 400 V supply.
Show answer
Qold = 10000 × 0.75 = 7500 var. Qnew = 10000 × 0.3287 ≈ 3287 var. Q_c = 7500 − 3287 ≈ 4213 var. C = 4213 / (2π × 50 × 400²) = 4213 / 50,265,482 ≈ 8.38 × 10⁻⁵ F, which is about 84 µF.
Exercise
The 230 V load from this chapter (P = 2645 W, Q = 2645 var) is fitted with a 200 µF capacitor at 50 Hz. Is the power factor lagging or leading, and why is this a poor choice?
Show answer
Q_c = 2π × 50 × 200×10⁻⁶ × 230² ≈ 3324 var, which is more than the load's 2645 var. Net Q = 2645 − 3324 ≈ −679 var, so the power factor is leading, about 0.97. This overcorrects. Source current is about 11.4 A, which is lower than before, but the leading power factor can raise the voltage and may be penalized by the tariff. A smaller capacitor such as 107 µF avoids this.