Sub topic 15
Distorted waveforms: displacement vs true power factor
This chapter assumes you know RMS values, phasors, the power triangle, and the definition of power factor (pf) as P/S. You should also know that a periodic waveform can be written as a sum of sinusoids (a Fourier series). The earlier chapters assumed pure sinusoids. Here the current is not sinusoidal, and the single "angle between voltage and current" no longer describes the load.
Why distortion matters
Loads such as rectifier power supplies, LED drivers, variable-speed drives, and computers draw current in pulses. The voltage at the outlet is close to a clean sine wave, but the current is not.
A distorted current still has an RMS value, real power, and apparent power. Two things change:
- Only part of the current contributes to real power.
- The ratio P/S can be low even when the current is exactly in phase with the voltage.
Harmonic decomposition
Any periodic current can be written as a fundamental at the line frequency plus harmonics at integer multiples of that frequency:
i(t) = √2 · [ I1 sin(ωt − φ1) + I3 sin(3ωt − φ3) + I5 sin(5ωt − φ5) + … ]
Here I1, I3, and I5 are RMS values of each component. The RMS value of the whole current is the root of the sum of squares:
Irms = √(I1² + I3² + I5² + …)
Harmonics add in power terms, not in amplitude terms. Two components with 3 A and 4 A RMS combine to 5 A, not 7 A.
Total harmonic distortion (THD) of the current compares the harmonic content with the fundamental:
THD_I = √(I3² + I5² + …) / I1
Which components deliver real power
Average power over one period is the average of v(t) · i(t). Sinusoids of different frequencies have zero average product over a full period. So only components at the same frequency contribute to real power:
P = Σ Vh Ih cos(φh)
Suppose the voltage is a pure sine wave at the fundamental. Then:
- Only the fundamental current produces real power: P = V · I1 · cos φ1.
- Harmonic currents add to Irms, and therefore to S, but add nothing to P.
- The harmonic currents still flow through the wiring and cause I²R heating.
Two power factors
The apparent power is still S = Vrms · Irms. The true power factor is the full ratio:
pf_true = P / S
Because P = V · I1 · cos φ1 and S = V · Irms, it splits into two factors:
pf_true = (I1 / Irms) · cos φ1
| Quantity | Formula | What it measures |
|---|---|---|
| Displacement power factor (DPF) | cos φ1 | Phase shift between the fundamental voltage and fundamental current |
| Distortion factor | I1 / Irms = 1 / √(1 + THD²) | Share of the RMS current that is at the fundamental frequency |
| True power factor | DPF × distortion factor | Real power divided by apparent power |
The relation between distortion factor and THD follows from Irms² = I1² · (1 + THD²).
For a pure sinusoid, THD is 0 and the distortion factor is 1, so the true pf equals the DPF from earlier chapters. Many meters and data sheets quote only the DPF, so check which one is meant.
The power tetrahedron: a third kind of "unused" power
With a sinusoidal current, S² = P² + Q². With harmonics, the fundamental reactive power is Q1 = V · I1 · sin φ1, and a leftover term appears:
S² = P² + Q1² + D²
D is the distortion power, in volt-amperes. It comes from the harmonic currents:
D = V · √(I3² + I5² + …)
These three terms are perpendicular, like the edges of a box. So S is the diagonal of a box rather than the hypotenuse of a flat triangle.
Worked example
A 230 V, 50 Hz supply is a pure sine wave. A load draws these current components:
- Fundamental: I1 = 10 A, lagging by 30°.
- Third harmonic: I3 = 4 A.
- Fifth harmonic: I5 = 3 A.
Step by step:
- Irms = √(10² + 4² + 3²) = √125 = 11.18 A.
- P = 230 × 10 × cos 30° = 1992 W.
- S = 230 × 11.18 = 2571 VA.
- pf_true = 1992 / 2571 = 0.7746.
- DPF = cos 30° = 0.8660, and the distortion factor is 10 / 11.18 = 0.8944. Their product is 0.7746, which matches step 4.
- THD_I = √(4² + 3²) / 10 = 5 / 10 = 50 %.
- Q1 = 230 × 10 × sin 30° = 1150 var.
- D = 230 × √(4² + 3²) = 230 × 5 = 1150 var.
- Check: P² + Q1² + D² = 3 967 500 + 1 322 500 + 1 322 500 = 6 612 500, and S² = 2571.48² = 6 612 500.
A meter that reports only DPF would show 0.866. The wiring carries current as if the pf were 0.775.
Verifying numerically
The script below builds the distorted current in the time domain. It averages v · i over one period and computes every quantity from the samples. The sample count of 2000 is far above twice the highest harmonic, so the averages of cross terms vanish.
import math
V = 230.0 # RMS voltage, pure sine at the fundamental
f = 50.0 # Hz
N = 2000 # samples over exactly one period
# (harmonic order, RMS current in A, phase lag in degrees)
harmonics = [(1, 10.0, 30.0), (3, 4.0, 10.0), (5, 3.0, 20.0)]
p_sum = 0.0
i_sq_sum = 0.0
for n in range(N):
t = n / (N * f)
v = math.sqrt(2) * V * math.sin(2 * math.pi * f * t)
i = sum(
math.sqrt(2) * Ih * math.sin(h * 2 * math.pi * f * t - math.radians(a))
for h, Ih, a in harmonics
)
p_sum += v * i
i_sq_sum += i * i
P = p_sum / N
Irms = math.sqrt(i_sq_sum / N)
S = V * Irms
pf_true = P / S
I1, _, phi1_deg = 10.0, None, 30.0
dpf = math.cos(math.radians(phi1_deg))
dist_factor = I1 / Irms
thd = math.sqrt(Irms**2 - I1**2) / I1
Q1 = V * I1 * math.sin(math.radians(phi1_deg))
D = math.sqrt(S**2 - P**2 - Q1**2)
print(f"P = {P:.0f} W, Irms = {Irms:.2f} A, S = {S:.0f} VA")
print(f"true pf = {pf_true:.4f}")
print(f"DPF = {dpf:.4f}, distortion factor = {dist_factor:.4f}")
print(f"THD = {thd * 100:.1f} %")
print(f"Q1 = {Q1:.0f} var, D = {D:.0f} var")The output shows P = 1992 W, S = 2571 VA, a true pf of 0.7746, a THD of 50.0 %, and Q1 and D both equal to 1150 var. These match the hand calculation.
What capacitor correction can and cannot do
A shunt capacitor supplies reactive power at the fundamental. It can cancel Q1, so the DPF can be brought to 1. It does not remove harmonic current drawn by the load, so D stays the same.
Continue the example and add a capacitor that supplies 1150 var:
- The fundamental source current drops to P / V = 8.66 A, in phase with the voltage.
- The harmonic currents are unchanged, so Irms = √(8.66² + 4² + 3²) = 10.0 A.
- S = 230 × 10 = 2300 VA, and the true pf = 1992 / 2300 = 0.866.
The ceiling on the true pf is P / √(P² + D²). Only filtering or a better load design can lift it. Options include an active power-factor-correction stage in the supply, a line reactor, or a harmonic filter.
Measurement and billing notes
- Use a true-RMS meter. Average-responding meters are calibrated for pure sinusoids and read wrong on distorted currents.
- A meter that reports "pf" may mean DPF or true pf. Compare P / S from the same instrument to find out.
- Utilities that penalize low pf usually define it on the basis of kW and kVA, so harmonic currents count against the customer.
- Three-phase loads with triplen harmonics (3rd, 9th, and so on) add in the neutral conductor rather than cancelling. A balanced three-phase load of single-phase rectifiers can load the neutral with more current than any phase.
Key points
- Only same-frequency voltage and current components deliver real power.
- Harmonic currents raise Irms and S without raising P.
- True pf = DPF × distortion factor.
- A distorted load has three perpendicular power terms: P, Q1, and D.
- Capacitors correct DPF and leave D unchanged.
Exercise
A 230 V pure-sine supply feeds a load whose current has a fundamental of 6 A in phase with the voltage (φ1 = 0°), a third harmonic of 3 A, and a fifth harmonic of 4 A. Find the real power, the apparent power, the DPF, the THD of the current, and the true power factor.
Show answer
Irms = √(6² + 3² + 4²) = √61 = 7.81 A. P = 230 × 6 × cos 0° = 1380 W. S = 230 × 7.81 = 1796 VA. DPF = cos 0° = 1.000. THD = √(3² + 4²) / 6 = 5 / 6 = 83.3 %. True pf = P / S = 1380 / 1796 = 0.768, which also equals 6 / 7.81. The current is in phase at the fundamental, yet the true pf is only 0.77, and no capacitor can improve it because Q1 is already zero.
Exercise
A load with a fundamental current of 10 A at 0.866 lagging and a harmonic current of 5 A (RMS, all harmonics combined) is supplied at 230 V. A capacitor bank is added to cancel Q1 exactly. What are the source current and true pf afterwards?
Show answer
P = 230 × 10 × 0.866 = 1992 W. After correction the fundamental source current is P / V = 8.66 A. Irms = √(8.66² + 5²) = √100 = 10.0 A. S = 2300 VA, and the true pf = 1992 / 2300 = 0.866. The source current falls from √(10² + 5²) = 11.18 A to 10.0 A, but the pf cannot exceed 0.866 because of the harmonic current.