Sub topic 12
Complex power S = V I* from phasors
This chapter assumes you can convert between rectangular and polar form, that you know impedance Z = R + jX, and that you know real power P, reactive power Q, apparent power S and power factor from the earlier chapters. All phasors here use RMS magnitudes unless stated otherwise.
Why one complex number is useful
Until now you have found P, Q and S separately. P comes from V I cos φ, Q from V I sin φ, and S from V I. Each needs its own trigonometry, and you must track the sign of φ yourself.
Complex power puts all three into one quantity. You multiply two phasors, and the real and imaginary parts of the product are P and Q. The magnitude is S, and the angle is the power factor angle.
The definition
For a load with RMS voltage phasor V and RMS current phasor I, complex power is:
S = V I*
The asterisk means the complex conjugate: keep the magnitude of I and flip the sign of its angle. Write the phasors in polar form:
- V = |V|∠θv
- I = |I|∠θi
- I* = |I|∠(−θi)
Then:
S = |V||I| ∠(θv − θi)
The angle of S is the voltage angle minus the current angle. That is exactly the power factor angle φ, the angle by which voltage leads current. So:
- |S| = |V||I| is the apparent power in VA.
- cos φ is the power factor.
- S = |S| cos φ + j |S| sin φ = P + jQ.
Why the conjugate is needed
Without the conjugate, V I would have the angle θv + θi. That sum has no physical meaning. Real and reactive power depend on the difference between the angles, and the conjugate produces the difference.
You can also see it from the time-domain result. With v(t) = √2 |V| cos(ωt + θv) and i(t) = √2 |I| cos(ωt + θi), the average of v(t) i(t) is |V||I| cos(θv − θi). That is the real part of V I*. The imaginary part, |V||I| sin(θv − θi), is the amplitude of the oscillating component of power that is exchanged with the fields.
Sign convention for Q
With S = V I*, the sign of Q tells you the type of load:
| Load | Current relative to voltage | Angle φ | Sign of Q |
|---|---|---|---|
| Inductive (R-L) | Lags | Positive | Positive |
| Capacitive (R-C) | Leads | Negative | Negative |
| Purely resistive | In phase | Zero | Zero |
A positive Q means the load absorbs reactive power, as an inductor does. A negative Q means the load supplies reactive power, as a capacitor does. This is the same lagging and leading classification from the previous chapter, now carried by the sign of a number.
Worked example: series R-L load
A 230 V RMS source drives a series R = 10 Ω and XL = 10 Ω. Take the source as the angle reference.
- V = 230∠0° V.
- Z = 10 + j10 = 14.142∠45° Ω.
- I = V / Z = 230∠0° / 14.142∠45° = 16.263∠−45° A.
- I* = 16.263∠+45° A.
- S = V I* = 230 × 16.263 ∠45° = 3740.5∠45° VA.
- In rectangular form, S = 2645 + j2645 VA.
So P = 2645 W, Q = 2645 var (inductive), |S| ≈ 3741 VA, and pf = cos 45° ≈ 0.7071 lagging. The code below repeats the calculation.
import cmath
import math
V = 230 + 0j # RMS voltage phasor, reference at 0 degrees
Z = 10 + 10j # series R = 10 ohm, XL = 10 ohm
I = V / Z # RMS current phasor
S = V * I.conjugate() # complex power
P = S.real # real power in W
Q = S.imag # reactive power in var (positive = inductive)
S_mag = abs(S) # apparent power in VA
pf = P / S_mag
print(f"I = {abs(I):.2f} A")
print(f"P = {P:.0f} W, Q = {Q:.0f} var, S = {S_mag:.0f} VA")
print(f"pf = {pf:.4f} {'lagging' if Q > 0 else 'leading'}")
print(f"angle = {math.degrees(cmath.phase(S)):.1f} degrees")The program prints a current of 16.26 A, P = 2645 W, Q = 2645 var, S = 3741 VA, pf = 0.7071 lagging, and an angle of 45.0 degrees.
The same load with a capacitor
Replace the inductor with a capacitor so that Z = 10 − j10 Ω. Then I = 230 / (10 − j10) = 11.5 + j11.5 A, which has an angle of +45°. The current now leads the voltage. Taking the conjugate gives I* = 11.5 − j11.5, so:
S = 230 × (11.5 − j11.5) = 2645 − j2645 VA
P is unchanged at 2645 W, because the resistor is the same. Q is now −2645 var, so the pf is 0.7071 leading.
Shortcuts from Ohm's law
Substituting V = Z I or I = V / Z into S = V I* gives forms that need only one phasor:
- S = |I|² Z, which means P = |I|² R and Q = |I|² X.
- S = |V|² / Z*, which uses the conjugate of the impedance.
Check the first form against the example: |I|² = 16.263² ≈ 264.5, and 264.5 × (10 + j10) = 2645 + j2645. This matches.
The first form shows that the resistive part of Z sets P and the reactive part sets Q. The second is useful for parallel branches, where the voltage is common and the currents differ.
Complex powers add
For a network of loads, the total complex power equals the sum of the complex powers of the individual loads. This holds whether the loads are in series or in parallel, because it follows from conservation of energy. P adds, and Q adds with its sign. The magnitudes |S| do not add unless every load has the same power factor angle.
Load A is the R-L load above, with S = 2645 + j2645 VA. Load B takes 1000 W at 0.8 leading power factor, so Q = −1000 × tan(acos 0.8) = −750 var, which gives S = 1000 − j750 VA.
import math
S_a = complex(2645, 2645)
P_b = 1000.0
Q_b = -P_b * math.tan(math.acos(0.8)) # leading load: negative Q
S_b = complex(P_b, Q_b)
S_total = S_a + S_b
pf = S_total.real / abs(S_total)
print(f"S_a = {abs(S_a):.0f} VA, S_b = {abs(S_b):.0f} VA")
print(f"sum of magnitudes = {abs(S_a) + abs(S_b):.0f} VA")
print(f"S_total = {S_total.real:.0f} W + j{S_total.imag:.0f} var")
print(f"|S_total| = {abs(S_total):.0f} VA")
print(f"pf = {pf:.4f} {'lagging' if S_total.imag > 0 else 'leading'}")The combined load is 3645 W and 1895 var. Its magnitude is about 4108 VA, and its power factor is about 0.887 lagging. The magnitudes alone sum to about 4991 VA, which is wrong by almost 900 VA. The capacitive load B cancels part of the reactive power of load A. This cancellation is the mechanism behind power factor correction, which comes later in this tutorial.
Common errors
- Mixing peak and RMS phasors. If V and I are peak values, the formulas change to S = ½ V I. Use RMS phasors throughout so that S = V I applies directly.
- Forgetting the conjugate on the impedance in S = |V|² / Z*. Using Z gives the wrong sign for Q.
- Adding apparent powers. Add the complex values, or add P and Q separately, and take the magnitude last.
- Taking the angle from the wrong place. The angle of S is θv − θi, not the angle of Z in a network. For a single impedance the two are equal, but for a combined network use the angle of the total S.
- Treating Q as a power that does work. The sign of Q is a bookkeeping convention. A negative Q does not mean negative work. It means the load supplies reactive power to the network.
Summary of the method
- Express V and I as RMS phasors, with a consistent reference angle.
- Compute S = V I, or use |I|² Z or |V|² / Z.
- Read P as the real part and Q as the imaginary part.
- Take |S| as the apparent power and P / |S| as the power factor.
- Use the sign of Q to label the power factor lagging (positive) or leading (negative).
Exercise
A load has a voltage phasor V = 120∠30° V (RMS) and a current phasor I = 5∠−30° A (RMS). Find S, P, Q, the power factor, and whether it is lagging or leading.
Show answer
I = 5∠+30° A. S = V I = 120 × 5 ∠(30° + 30°) = 600∠60° VA. P = 600 cos 60° = 300 W. Q = 600 sin 60° ≈ 520 var. The power factor is cos 60° = 0.5. Q is positive and the current lags the voltage by 60°, so the power factor is lagging (inductive load).
Exercise
Two loads share the same supply. Load 1 has S1 = 4000 + j3000 VA. Load 2 is capacitive, takes 2000 W, and has a power factor of 0.6 leading. Find the total P, Q, |S| and the combined power factor. Why is |S| less than the sum of the individual apparent powers?
Show answer
For load 2, S2 = P / pf = 2000 / 0.6 ≈ 3333 VA, and Q2 = −P tan(acos 0.6) = −2000 × 1.333 ≈ −2667 var. So S2 = 2000 − j2667 VA. The total is S = 6000 + j333 VA, so P = 6000 W, Q ≈ 333 var, and |S| ≈ 6009 VA. The combined power factor is 6000 / 6009 ≈ 0.998 lagging. The apparent powers are 5000 VA and 3333 VA, which sum to 8333 VA. The total is smaller because the negative Q of the capacitive load cancels most of the positive Q of load 1. Complex powers add, but magnitudes do not.