Sub topic 10
Power factor and why utilities care
This chapter assumes you can compute RMS values, write voltage and current as phasors, and read real power P, reactive power Q, and apparent power S off the power triangle. You should also be comfortable with complex numbers in polar form.
Definition
Power factor (pf) is the ratio of real power to apparent power:
pf = P / SP is the average power that does work, in watts. S is the product of RMS voltage and RMS current, in volt-amperes. Since P can never exceed S, the power factor lies between 0 and 1.
For purely sinusoidal voltage and current, the power triangle gives P = S cos φ. In that case pf equals cos φ, where φ is the phase angle between voltage and current. A resistive load has φ = 0 and pf = 1. A pure inductor or capacitor has φ = ±90° and pf = 0.
The ratio P/S is the more general definition. The cos φ form holds only for sinusoids. The last chapters of this tutorial return to that distinction for distorted waveforms.
A worked example
Take the load from the earlier chapters: a 230 V RMS source across a series R-L load with Z = 10 + j10 Ω.
- The current is I = 230 / (10 + j10), so |I| = 230 / 14.142 = 16.26 A.
- The apparent power is S = 230 × 16.26 = 3741 VA.
- The real power is P = I²R = 16.26² × 10 = 2645 W.
- The power factor is 2645 / 3741 = 0.7071, which is cos 45°.
Only 71% of the volt-amperes the source supplies turn into useful power. The source and wiring must still carry the full 16.26 A.
Why the current matters
Wires, transformers, and generators are limited by current, not by watts. Heating in a conductor depends on I²R, and insulation and magnetic cores are rated by the current and voltage they can tolerate. For a fixed real power and voltage, the current is:
I = P / (V × pf)A lower power factor therefore forces a higher current to deliver the same watts. The table shows this for the 2645 W load at 230 V.
| Power factor | Current (A) | Apparent power (VA) | Line loss relative to pf = 1 |
|---|---|---|---|
| 1.00 | 11.50 | 2645 | 1.00 |
| 0.95 | 12.11 | 2784 | 1.11 |
| 0.80 | 14.38 | 3306 | 1.56 |
| 0.71 | 16.26 | 3741 | 2.00 |
| 0.50 | 23.00 | 5290 | 4.00 |
The last column is 1/pf². At pf = 0.5 the same useful power costs four times the line loss. The loss scales with the square of the current, so a modest drop in pf is expensive.
The following script reproduces the table.
P = 2645.0 # W, real power delivered to the load
V = 230.0 # V RMS
print(f"{'pf':>5} {'I (A)':>7} {'S (VA)':>8} {'loss ratio':>11}")
for pf in [1.0, 0.95, 0.8, 0.7071, 0.5]:
I = P / (V * pf)
S = V * I
loss_ratio = 1 / pf**2
print(f"{pf:5.2f} {I:7.2f} {S:8.0f} {loss_ratio:11.2f}")What the utility sees
The utility supplies current at a nearly fixed voltage, so it experiences a customer's power factor through the current. Three effects follow.
- Losses. Every conductor between the generator and the customer dissipates I²R. A low-pf customer raises that loss in lines and transformers the utility owns, and the utility pays for the energy lost.
- Voltage drop. Line current flowing through line impedance lowers the voltage at the customer. Lagging reactive current is especially bad here because the line reactance is mostly inductive. Voltage regulation gets harder as reactive demand grows.
- Capacity. Generators, transformers, and cables are rated in kVA. A feeder rated at 100 kVA can deliver 100 kW at pf = 1, but only 70 kW at pf = 0.7. The rest of its capacity carries current that does no work, so the utility cannot sell that capacity to other customers.
The utility meters energy in kWh, and a kWh meter does not see the extra current. Many commercial and industrial tariffs therefore add another term. Some bill for peak demand in kVA instead of kW. Others apply a surcharge when the monthly pf falls below a threshold, often somewhere between 0.85 and 0.95. The exact rules vary by region and contract. Check the tariff before sizing any correction.
Residential customers are usually billed in kWh only. Their small reactive loads are averaged across many homes, and the utility manages the effect on the whole network.
Power factor is not efficiency
A low power factor does not mean the load wastes energy. The load in the example turns all of its 2645 W into heat and work, and it dissipates nothing in the reactive part. Reactive power Q is exchanged with the magnetic field of the inductance and returns to the source each cycle. The waste appears in the supply path, because the current carrying Q still heats the wires.
Efficiency is output power divided by input power. Power factor is real power divided by apparent power. A motor can have 95% efficiency and a power factor of 0.8, or the reverse.
Specifying a power factor correctly
A single number does not fully describe a load. A load with pf = 0.8 might be inductive or capacitive, and the two have opposite effects on Q. The convention is to add the word lagging or leading:
- Lagging means the current lags the voltage, so the load is inductive and Q > 0.
- Leading means the current leads the voltage, so the load is capacitive and Q < 0.
The earlier chapter on lagging and leading loads covers this in more detail. For now, note that the example above is a lagging pf of 0.7071.
Most real loads lag. Induction motors, transformers, and fluorescent ballasts all need magnetizing current, so a plant full of them presents a lagging pf. Lightly loaded motors are worse, because the magnetizing current stays the same while real power falls. A motor running at 25% load can have a pf of 0.5 or less.
Edge cases
- Zero current. pf is undefined when S = 0. Instruments usually display 0 or a blank when the load is off.
- Negative real power. If a load pushes real power back to the source, as a generator or inverter does, P is negative. Metering standards then specify a sign convention for pf, so check which one your instrument uses.
- Distorted current. Rectifiers and switching supplies draw non-sinusoidal current. Then P/S is smaller than cos φ of the fundamental, because harmonic currents add to the RMS current without adding to P. Meters that report only "cos φ" may overstate the true power factor.
- Light loading. Because motor magnetizing current is nearly constant, the power factor depends on load level. Quote a power factor together with the operating point.
Summary of the key relationships
| Quantity | Formula | Example value |
|---|---|---|
| Power factor | P / S | 0.7071 |
| Sinusoidal case | cos φ | cos 45° |
| Line current | P / (V × pf) | 16.26 A |
| Loss relative to pf = 1 | 1 / pf² | 2.00 |
| Usable real power from a kVA rating | S_rated × pf | 70 kW from 100 kVA at pf = 0.7 |
Exercise
A 230 V single-phase load draws 4600 W at a lagging pf of 0.8. (a) What is the line current? (b) The supply cable has 0.1 Ω of total resistance. What is the cable loss, and what would it be if the pf were corrected to 1.0 with the same 4600 W?
Show answer
(a) I = P / (V × pf) = 4600 / (230 × 0.8) = 25 A. (b) The loss at pf = 0.8 is I²R = 25² × 0.1 = 62.5 W. At pf = 1.0 the current is 4600 / 230 = 20 A, so the loss is 20² × 0.1 = 40 W. The ratio 40 / 62.5 = 0.64 equals 0.8², as 1/pf² predicts.
Exercise
A transformer is rated 50 kVA. How much real power can it supply to a load with a lagging pf of 0.75 before it reaches its rating? If the pf is raised to 0.95, how much more real power can it supply?
Show answer
At pf = 0.75, P = 50 kVA × 0.75 = 37.5 kW. At pf = 0.95, P = 50 × 0.95 = 47.5 kW. The correction frees an extra 10 kW of capacity without replacing the transformer.
Exercise
A plant has two loads on the same supply. Load A takes 30 kW at pf 0.8 lagging. Load B takes 20 kW at pf 0.6 lagging. What is the combined power factor?
Show answer
Load A has Q = 30 × tan(acos 0.8) = 30 × 0.75 = 22.5 kvar. Load B has Q = 20 × tan(acos 0.6) = 20 × 1.333 = 26.67 kvar. The totals are P = 50 kW and Q = 49.17 kvar, so S = sqrt(50² + 49.17²) = 70.1 kVA. The combined pf = 50 / 70.1 = 0.713 lagging. It is not the average of 0.8 and 0.6 weighted by anything simple, so you must add P and Q.