Sub topic 14
Power in Balanced Three-Phase Systems
Large loads and almost all generation and transmission use three-phase power. This chapter extends the single-phase quantities P, Q, S, and power factor to balanced three-phase systems. It assumes you know phasors, impedance, complex power S = V I*, and the power triangle from earlier chapters. You should also be comfortable with complex numbers in polar form.
What "balanced three-phase" means
A three-phase source has three voltages of equal magnitude, each shifted by 120° from the next. A balanced system has two properties:
- The three source voltages have equal magnitude and 120° spacing.
- The three load impedances are identical.
Under these conditions the three phases carry equal currents, also 120° apart. You can analyze one phase and multiply by three. This is the per-phase method.
Wye and delta connections
A load, or a source winding set, is connected in one of two ways.
- Wye (Y): each impedance sits between a line and a common neutral point.
- Delta (Δ): each impedance sits between two lines.
Two kinds of quantity must be kept apart:
- Line quantities are measured between lines, or in a line conductor. They are VL and IL.
- Phase quantities are measured across or through one load impedance. They are Vph and Iph.
| Connection | Voltage relation | Current relation |
|---|---|---|
| Wye | V_L = √3 V_ph | I_L = I_ph |
| Delta | V_L = V_ph | I_L = √3 I_ph |
In a wye connection the line voltage is √3 times the phase voltage because two phase voltages 120° apart are subtracted. A 400 V line-to-line system has 400/√3 ≈ 230.9 V from each line to neutral. The delta current relation follows from the same subtraction applied to currents.
Total power
For one phase, the single-phase results apply directly:
- Pph = Vph I_ph cos φ
- Qph = Vph I_ph sin φ
- Sph = Vph I_ph
Here φ is the angle between the phase voltage and the phase current. It equals the angle of the load impedance. Multiply by three for the total:
- P = 3 Vph Iph cos φ
- Q = 3 Vph Iph sin φ
- S = 3 Vph Iph
Substituting the wye or delta relations from the table gives the same result in terms of line quantities:
- P = √3 VL IL cos φ
- Q = √3 VL IL sin φ
- S = √3 VL IL
These line-quantity formulas hold for both wye and delta. That is why they are the standard form on nameplates and in datasheets. The power triangle is unchanged: S² = P² + Q², and pf = P/S = cos φ. In complex form, S = 3 Vph Iph*, or equivalently S = √3 VL IL ∠φ.
Why three-phase power is smooth
In a single-phase circuit, p(t) = v(t) i(t) oscillates at twice the supply frequency, as you saw in the instantaneous power chapter. In a balanced three-phase circuit, the three phases produce three such oscillating terms. Their oscillating parts are shifted by 120° of the supply cycle, which is 240° of the double-frequency term, so they cancel. The sum is:
pa(t) + pb(t) + pc(t) = 3 Vph I_ph cos φ = P
The total instantaneous power is constant and equals the real power. This is why three-phase motors deliver steady torque with no double-frequency pulsation. A single-phase motor has torque pulsation that three-phase machines avoid.
Reactive power does not vanish in the same way. Each phase still exchanges energy with its fields. In a balanced system, the energy leaving one phase's inductance flows into the other phases, so the net exchange with the source is zero at every instant. The source still carries the currents that make this exchange possible, so Q still raises S and the line current.
Worked example: the same impedance in wye and delta
A 400 V (line-to-line), 50 Hz supply feeds a balanced load with Z = 10 + j10 Ω in each phase, so |Z| = 14.14 Ω and φ = 45°. The code below computes the wye case, then the delta case, using complex phasors.
import math
V_L = 400.0
Z = 10 + 10j
def report(name, S_total, I_line):
P, Q = S_total.real, S_total.imag
S = abs(S_total)
print(f"{name}: I_line = {abs(I_line):.2f} A, P = {P:.0f} W, "
f"Q = {Q:.0f} var, S = {S:.0f} VA, pf = {P / S:.4f}")
# Wye: each impedance sees the line-to-neutral voltage.
V_an = V_L / math.sqrt(3)
I_a = V_an / Z
report("wye ", 3 * V_an * I_a.conjugate(), I_a)
# Delta: each impedance sees the full line-to-line voltage.
V_ab = V_L
I_ab = V_ab / Z
I_line = math.sqrt(3) * I_ab # same magnitude as the line current
report("delta", 3 * V_ab * I_ab.conjugate(), I_line)The results are:
| Connection | Phase voltage | Line current | P | Q | S | pf |
|---|---|---|---|---|---|---|
| Wye | 230.9 V | 16.33 A | 8000 W | 8000 var | 11314 VA | 0.7071 lagging |
| Delta | 400 V | 48.99 A | 24000 W | 24000 var | 33941 VA | 0.7071 lagging |
You can verify the wye result by hand: P = 3 I² R = 3 × 16.33² × 10 ≈ 8000 W. The delta result is exactly three times larger. Each delta impedance sees √3 times the voltage, so its current is √3 times larger and its power is 3 times larger. The power factor is the same in both cases because it depends only on the impedance angle.
Power factor correction in three phases
Correcting power factor works as in the single-phase case, but the reactive power to remove is the three-phase total. Take the wye load above (P = 8000 W, pf = 0.7071) and raise the power factor to 0.95. The code finds the total reactive power needed, then the capacitance per phase for each capacitor connection.
import math
P = 8000.0 # W, total real power
V_L = 400.0 # V, line-to-line
f = 50.0 # Hz
pf_old = 0.7071
pf_new = 0.95
Q_old = P * math.tan(math.acos(pf_old))
Q_new = P * math.tan(math.acos(pf_new))
Q_c = Q_old - Q_new # total reactive power the bank must supply
Q_c_phase = Q_c / 3 # per capacitor
w = 2 * math.pi * f
C_delta = Q_c_phase / (w * V_L**2) # each capacitor across V_L
C_wye = Q_c_phase / (w * (V_L / math.sqrt(3))**2) # each across V_L / sqrt(3)
print(f"Qc total = {Q_c:.0f} var, per phase = {Q_c_phase:.0f} var")
print(f"delta bank: {C_delta * 1e6:.1f} microfarads per capacitor")
print(f"wye bank: {C_wye * 1e6:.1f} microfarads per capacitor")The bank must supply about 5370 var in total, or about 1790 var per phase. A capacitor supplies Q = ω C V², so the capacitance depends on the voltage across it. A delta-connected bank needs about 35.6 µF per capacitor. A wye-connected bank needs about 106.8 µF, three times as much, because each capacitor sees only V_L/√3. Both banks supply the same total reactive power. The delta bank uses smaller capacitors at a higher voltage rating. The wye bank uses larger capacitors at a lower voltage rating.
Why utilities care in three-phase systems
The line current is IL = P / (√3 VL cos φ). For a fixed P and V_L, a low power factor raises the line current. That current produces I²R losses in every one of the three conductors and in the transformers. This is the same argument as in the single-phase case, applied to three conductors. A three-phase system also needs less conductor material than three separate single-phase circuits delivering the same power. It uses three conductors instead of six.
Common errors
- Using VL where the formula needs Vph. In P = 3 Vph Iph cos φ, the voltage must be the one across a single impedance.
- Writing P = √3 VL IL without cos φ. That expression is S.
- Using the angle between line quantities as φ.
- Applying the per-phase method to an unbalanced load. The 120° symmetry that makes the shortcut work no longer holds. Unbalanced systems need symmetrical components or a full mesh or nodal analysis.
- Forgetting that a three-phase power-factor correction bank is rated in total var, which you must split across three capacitors.
Exercise
A balanced three-phase motor on a 400 V line-to-line supply draws 20 kW at a power factor of 0.8 lagging. Find the apparent power, the reactive power, and the line current.
Show answer
S = P / pf = 20000 / 0.8 = 25000 VA = 25 kVA. Q = √(S² − P²) = √(25000² − 20000²) = 15000 var = 15 kvar, lagging. The line current is IL = S / (√3 VL) = 25000 / (1.732 × 400) ≈ 36.1 A. You get the same value from IL = P / (√3 VL pf) = 20000 / (1.732 × 400 × 0.8) ≈ 36.1 A.
Exercise
The motor in the previous exercise needs its power factor raised to 0.95. How much total reactive power must a capacitor bank supply, and what is that per phase?
Show answer
Qold = 15000 var. Qnew = P tan(acos 0.95) = 20000 × 0.3287 ≈ 6574 var. The bank supplies Q_c = 15000 − 6574 ≈ 8426 var in total, which is about 2809 var per phase.