Sub topic 7
Reactive Power: Energy Exchanged with Fields
This chapter assumes you can write a sinusoid as a phasor, know that an inductor has reactance XL = ωL and a capacitor has XC = 1/(ωC), and have met instantaneous power p(t) = v(t) i(t) and real power P. We now isolate the part of p(t) that averages to zero and explain why it still matters.
Splitting p(t) into two parts
Take v(t) = √2 V cos(ωt) and i(t) = √2 I cos(ωt − φ). V and I are RMS values. φ is the angle by which current lags voltage, so φ is positive for an inductive load. Applying the product-to-sum identity gives:
p(t) = V I cos φ (1 + cos 2ωt) + V I sin φ sin 2ωt
The first term never goes negative. It averages to P = V I cos φ and carries energy from source to load. The second term swings symmetrically about zero at twice the line frequency. Its peak value is the reactive power:
Q = V I sin φ
The unit is the volt-ampere reactive (var), not the watt. The average of the second term over a cycle is zero. Over each half of its swing, energy flows into the load's magnetic or electric field and then flows back to the source.
The energy picture
An inductor stores W = ½ L i² in its magnetic field. A capacitor stores W = ½ C v² in its electric field. Neither element consumes net energy, so both contribute only to Q.
For an ideal inductor carrying RMS current I, the average stored energy is ½ L I². The peak is L I². Then:
QL = I² XL = I² ωL = 2ω × (average stored energy)
So reactive power measures how fast energy is being exchanged with the field. It is not a rate of consumption. The peak energy that sloshes back and forth each cycle is Q/ω.
Sign convention
Engineers agree on a sign so that reactive powers can be added.
| Element | Voltage-current relation | φ (current lag) | Q |
|---|---|---|---|
| Resistor | In phase | 0° | 0 |
| Inductor | Current lags by 90° | +90° | +I² X_L = +V²/X_L |
| Capacitor | Current leads by 90° | −90° | −I² X_C = −V²/X_C |
Inductive loads absorb Q (positive). Capacitive loads supply Q (negative). Some textbooks flip this convention, so check which one yours uses before comparing numbers.
Worked example: series R-L load
A 230 V RMS source drives R = 10 Ω in series with X_L = 10 Ω.
- |Z| = √(10² + 10²) = 14.142 Ω, and the angle of Z is 45°.
- I = 230 / 14.142 = 16.263 A, lagging V by 45°.
- P = I² R = 264.5 × 10 = 2645 W.
- Q = I² X_L = 264.5 × 10 = 2645 var. The check V I sin φ = 230 × 16.263 × 0.7071 gives the same value.
- L = X_L / ω = 10 / 314.16 = 31.83 mH. The peak field energy is L I² = 0.03183 × 264.5 = 8.42 J. As a check, Q/ω = 2645 / 314.16 = 8.42 J.
The next script confirms this numerically. It builds p(t) from sampled waveforms and extracts Q by correlating p(t) with sin 2ωt. That correlation picks out the reactive term, because the other terms are orthogonal to it over a whole period. It also finds the peak inductor energy by sampling ½ L i².
import math
Vrms = 230.0
R, X = 10.0, 10.0
f = 50.0
w = 2 * math.pi * f
Irms = Vrms / math.hypot(R, X)
phi = math.atan2(X, R) # current lags voltage by phi
L = X / w
N = 1000 # samples over exactly one period
q_corr = 0.0
peak_energy = 0.0
for n in range(N):
t = n / (N * f)
v = math.sqrt(2) * Vrms * math.cos(w * t)
i = math.sqrt(2) * Irms * math.cos(w * t - phi)
p = v * i
q_corr += p * math.sin(2 * w * t)
peak_energy = max(peak_energy, 0.5 * L * i * i)
Q_est = 2 * q_corr / N
print(f"Q from p(t) correlation = {Q_est:.0f} var")
print(f"Q = V*I*sin(phi) = {Vrms * Irms * math.sin(phi):.0f} var")
print(f"peak inductor energy = {peak_energy:.2f} J")
print(f"Q / omega = {Vrms * Irms * math.sin(phi) / w:.2f} J")All three routes agree: Q = 2645 var and 8.42 J of peak energy.
Reactive power adds algebraically
Real power adds across loads, and so does reactive power, as long as you keep the signs. The magnitude S does not add. For any set of loads on the same voltage:
Ptotal = ΣPk, Qtotal = ΣQk (signed), Stotal = √(Ptotal² + Q_total²)
Suppose load A is the 2645 W, +2645 var load above. Load B is a capacitive load with P = 1000 W and Q = −600 var.
| Quantity | Load A | Load B | Total |
|---|---|---|---|
| P (W) | 2645 | 1000 | 3645 |
| Q (var) | +2645 | −600 | +2045 |
| S (VA) | 3741 | 1166 | 4180 |
Adding the individual S values would give 4907 VA, which is wrong. Load B cancels part of A's reactive power, so the true S is 4180 VA. This cancellation is the basis of power factor correction, which a later chapter covers.
Why a power that "does no work" still matters
Q does no net work, but the current that carries it flows through the same wires, transformers, and generator windings as the real current. That current has two effects:
- Conductor heating. Losses are I² R_line. For the load above, the line current is 16.26 A. A unity-power-factor load delivering the same 2645 W at 230 V would need only 2645 / 230 = 11.5 A. With a 0.5 Ω line, losses are 132 W against 66 W, so the reactive current doubles them.
- Voltage drop and capacity. The reactive current reduces the voltage at the load end, and it uses up the current rating of equipment. A transformer rated in kVA must carry S, not P.
Because of this, utilities often bill large customers for kVA demand or penalize low power factor, even though they only meter real energy in kWh at the household level.
Common errors
- Using the wrong angle. φ is the angle between voltage and current, not the angle of Z in a delta or the angle of the current alone. For an impedance Z = R + jX, φ = arctan(X/R). The angle of Z equals φ only when the voltage is the reference.
- Mixing units. Write Q in var (kvar, Mvar). Writing W for Q hides which quantity you mean, and instruments and nameplates keep them separate.
- Dropping the sign. If you compute Q = V I sin φ with φ taken from a formula that gives only magnitudes, you lose the inductive-versus-capacitive information. Keep φ signed, or apply the table above.
- Adding S arithmetically. As the example showed, only P and Q add.
- Confusing the frequency of the oscillation. The reactive term in p(t) swings at 2ω, which is 100 Hz on a 50 Hz system. The energy exchange between source and field therefore happens twice per voltage cycle.
- Assuming a resistor-only load has Q = 0 at all frequencies. This holds for an ideal resistor. Real wire-wound resistors have some inductance, so at high frequency they draw small amounts of Q.
Check yourself
Exercise
A load draws P = 1200 W and S = 2000 VA from a single-phase supply. Find Q and the power factor. Can you tell from these numbers alone whether the load is inductive or capacitive?
Show answer
Q = √(S² − P²) = √(2000² − 1200²) = 1600 var in magnitude. The power factor is P/S = 1200/2000 = 0.6. No, you cannot tell the sign from P and S alone. Both an inductive load (Q = +1600 var, lagging) and a capacitive load (Q = −1600 var, leading) give the same magnitudes. You need the phase of the current relative to the voltage, or the sign of Q.
Exercise
An ideal 20 mH inductor is connected across a 120 V RMS, 60 Hz source. Find its reactive power and the peak energy stored in its magnetic field.
Show answer
XL = 2π × 60 × 0.020 = 7.54 Ω. The current is I = 120 / 7.54 = 15.92 A. Q = V² / XL = 14400 / 7.54 ≈ 1910 var (positive, inductive). The peak stored energy is L I² = 0.020 × 15.92² ≈ 5.07 J. This agrees with Q/ω = 1910 / 376.99 ≈ 5.07 J.
Exercise
A line has resistance 0.5 Ω. A load takes 2645 W at 230 V with a power factor of 0.7071 lagging. By what factor would the line loss fall if the load's power factor were raised to 1 with P and V unchanged?
Show answer
At pf 0.7071 the current is 2645 / (230 × 0.7071) = 16.26 A, so the loss is 16.26² × 0.5 ≈ 132 W. At pf 1 the current is 2645 / 230 = 11.5 A, so the loss is 11.5² × 0.5 ≈ 66 W. The loss falls by a factor of 2, because the loss scales with 1/pf² (1/0.7071² = 2).