Sub topic 17
The transformer and power transmission
This chapter assumes you know Faraday's law, mutual inductance, and rms values of AC. It also assumes you can use P = VI and P = I²R.
What a transformer does
A transformer changes the amplitude of an AC voltage with almost no loss of power. It has two coils, the primary and the secondary, wound on a common soft-iron core. The core carries nearly all the magnetic flux produced by the primary to the secondary.
The working principle is mutual induction. An alternating current in the primary makes an alternating flux in the core. That changing flux links the secondary and induces an emf in it. A transformer works only with AC, because a steady DC current produces a constant flux, and a constant flux induces no emf.
The ideal transformer
Assume no flux leaks out of the core and no energy is lost. The same flux Φ then links every turn of both coils. By Faraday's law, each turn has an emf of dΦ/dt. With Np primary turns and Ns secondary turns:
- Primary: ep = −Np dΦ/dt
- Secondary: es = −Ns dΦ/dt
Dividing gives the turns-ratio relation:
Vs / Vp = Ns / Np = K
K is the turns ratio. An ideal transformer wastes no power, so Vp Ip = Vs Is. Combining this with the voltage relation gives:
Ip / Is = Ns / Np = Vs / Vp
| Type | Turns | Secondary voltage | Secondary current |
|---|---|---|---|
| Step-up | Ns > Np (K > 1) | Larger than primary | Smaller than primary |
| Step-down | Ns < Np (K < 1) | Smaller than primary | Larger than primary |
A transformer never steps up power. If it raises the voltage, it lowers the current by the same factor.
Real transformers: energy losses
Real efficiency is the output power divided by the input power:
η = (Vs Is) / (Vp Ip)
Efficiency in a good transformer is often above 95%. The losses and the usual remedies are:
| Loss | Cause | Remedy |
|---|---|---|
| Copper loss | I²R heating in the windings | Thick wire, especially on the low-voltage, high-current winding |
| Eddy current loss | Induced currents circulating in the core | Laminated core, with thin insulated sheets |
| Hysteresis loss | Energy spent re-magnetising the core every cycle | Soft iron, which has a narrow hysteresis loop |
| Flux leakage | Some flux does not link both coils | Wind the coils over each other on a closed core |
| Humming | Magnetostriction, where the core changes size slightly with the flux | Tight clamping of the core |
Eddy currents are the induced currents you met earlier. Cutting the core into insulated laminates breaks up their loops and raises their resistance, so they shrink.
Why power is sent at high voltage
A power station must deliver a fixed power P to a distant town through lines of total resistance R. The line current is I = P / V, where V is the transmission voltage. The power wasted as heat in the lines is:
P_loss = I²R = (P / V)² R
The loss varies as 1/V². Doubling the voltage cuts the loss to a quarter.
A worked case: deliver 100 kW through lines with R = 5 Ω.
| Transmission voltage | Line current | Line loss | Fraction lost |
|---|---|---|---|
| 2 kV | 50 A | 12.5 kW | 12.5% |
| 20 kV | 5 A | 125 W | 0.125% |
Raising the voltage tenfold cuts the loss a hundredfold. This is why the power station uses a step-up transformer. Step-down transformers then lower the voltage near the town, first for substations and finally to 220 V for homes.
AC is used for distribution because a transformer can change its voltage easily and efficiently. Changing a DC voltage this way is not possible.
Computing transformer and line behaviour
This program applies the ideal-transformer relations with an efficiency factor. It also compares line losses at several transmission voltages.
def transformer(vp, n_primary, n_secondary, i_load, efficiency=1.0):
"""Return secondary voltage, output power, input power, primary current."""
vs = vp * n_secondary / n_primary
p_out = vs * i_load
p_in = p_out / efficiency
ip = p_in / vp
return vs, p_out, p_in, ip
def line_loss(power, voltage, line_resistance):
"""Heat lost in the transmission line for a given delivered power."""
current = power / voltage
return current, current ** 2 * line_resistance
vs, p_out, p_in, ip = transformer(220, 100, 1000, 2.0, efficiency=0.9)
print(f"Vs = {vs:.0f} V, Pout = {p_out:.0f} W, Pin = {p_in:.1f} W, Ip = {ip:.2f} A")
for v in (2_000, 20_000, 200_000):
i, loss = line_loss(100_000, v, 5.0)
print(f"V = {v:>7} V, I = {i:6.2f} A, loss = {loss:9.2f} W")In the first call the secondary is 2200 V and the load draws 2 A. The output power is 4400 W. At 90% efficiency the primary draws about 4888.9 W, which is 22.22 A at 220 V.
Common errors in NEET problems
- Inverting the ratio. The voltage ratio is Vs/Vp = Ns/Np, but the current ratio is Is/Ip = Np/Ns. Current is inverse to voltage.
- Using the transformer on DC. A battery connected to the primary gives no steady secondary voltage.
- Thinking a step-up transformer gains power. Output power cannot exceed input power. Only the voltage-to-current balance changes.
- Using the wrong voltage in the loss formula. Line loss is I²R, with I = P/V at the transmission voltage. It is not V²/R, because V is not the voltage drop across the line wires.
- Forgetting efficiency in the current. If η < 1, then Ip = Pout / (η Vp), not Pout / Vp.
- Mixing rms and peak values. Transformer ratios hold for peak, rms, or instantaneous values, but do not mix them within one calculation.
Exercises
Exercise
A step-down transformer has 2200 V across its primary and delivers 220 V to a load drawing 10 A. Its efficiency is 80%. Find the primary current.
Show answer
Output power = 220 × 10 = 2200 W. Input power = 2200 / 0.8 = 2750 W. Primary current Ip = 2750 / 2200 = 1.25 A. (An ideal transformer would draw 1 A.)
Exercise
A power station sends 50 kW through a line of resistance 8 Ω. Compare the line loss when the power is sent at 500 V with the loss when it is sent at 5000 V.
Show answer
At 500 V: I = 50000 / 500 = 100 A, so loss = 100² × 8 = 80 000 W. That is more than the 50 kW being sent, so the system is not feasible. At 5000 V: I = 10 A, so loss = 10² × 8 = 800 W, which is 1.6% of the power. A tenfold rise in voltage cuts the loss a hundredfold.
Exercise
A transformer has 400 primary turns and 2000 secondary turns. Why can it not be used to light a lamp from a 12 V battery, and what would it give from a 12 V rms AC source?
Show answer
A battery gives DC, which produces a constant flux and so no induced emf in the secondary. From a 12 V rms AC source, Vs = 12 × 2000 / 400 = 60 V rms.