Sub topic 9
Resistivity, length, and cross-section
This chapter assumes you can rearrange algebraic equations, use SI prefixes, and apply V = IR. It also assumes you know what resistance is. Here you learn what sets the resistance of a uniform wire or bar: the material, the length, and the cross-sectional area.
Resistance depends on the object, resistivity on the material
Resistance (R, in ohms) describes one specific piece of conductor. A short thick copper rod and a long thin copper wire are the same material, yet their resistances differ by orders of magnitude. Resistivity (symbol ρ, the Greek letter rho) describes the material itself. Its SI unit is the ohm-metre (Ω·m).
For a uniform conductor with current flowing along its length:
R = ρ · L / A
- ρ is the resistivity in Ω·m.
- L is the length along the current path in metres.
- A is the cross-sectional area, perpendicular to the current, in square metres.
The equation matches physical intuition about current flowing through a pipe:
- Doubling the length doubles R. Charge carriers collide with the material for twice as long.
- Doubling the area halves R. The current has twice as many parallel paths.
- A material with a higher ρ gives a higher R for the same shape.
Typical resistivity values
Resistivities span about 24 orders of magnitude, which is far more than most physical quantities. The values below are approximate and refer to about 20 °C.
| Material | Resistivity ρ (Ω·m) | Category |
|---|---|---|
| Silver | 1.6 × 10⁻⁸ | Conductor |
| Copper | 1.68 × 10⁻⁸ | Conductor |
| Aluminium | 2.8 × 10⁻⁸ | Conductor |
| Nichrome | 1.1 × 10⁻⁶ | Resistive alloy |
| Silicon (pure) | roughly 2 × 10³ | Semiconductor |
| Glass | 10¹⁰ to 10¹⁴ | Insulator |
Silicon's value varies widely with purity and doping, so treat it as an order of magnitude only. Nichrome is about 65 times more resistive than copper, which is why heating elements use it. A heater wire needs high resistance so that I²R produces useful heat.
A worked calculation
Take 1 m of copper wire with a cross-section of 1 mm². Convert the area to square metres first: 1 mm² = 1 × 10⁻⁶ m². This conversion is the most common source of mistakes (see the errors section below).
rho_copper = 1.68e-8 # ohm-metres, approximate value at 20 C
length = 1.0 # metres
area = 1.0e-6 # square metres (1 mm^2)
R = rho_copper * length / area
print(f"R = {R:.4f} ohm") # about 0.0168 ohmThe result is about 0.017 Ω per metre. Now see what this does in a real circuit. Suppose a 10 A load is wired with a 20 m run of this wire. The current flows out and back, so the total conductor length is 40 m.
- R = 0.0168 Ω/m × 40 m = 0.672 Ω
- Voltage drop = I · R = 10 A × 0.672 Ω = 6.72 V
- Power lost as heat in the wire = I²R = 100 × 0.672 = 67.2 W
On a 12 V supply, a 6.72 V drop is unacceptable. The load would get under half the supply voltage. This is why low-voltage, high-current wiring needs thick cable. Increasing the cross-section to 6 mm² cuts the resistance by a factor of 6, so the drop falls to about 1.12 V.
Area from diameter
Wires are usually specified by diameter, not area. For a round wire:
A = π · d² / 4
Because area depends on the square of the diameter, a small change in diameter has a large effect on resistance. Doubling the diameter quadruples the area and cuts resistance to a quarter.
import math
def wire_resistance(rho, length_m, diameter_m):
area = math.pi * diameter_m ** 2 / 4.0
return rho * length_m / area
rho_copper = 1.68e-8
for d_mm in (0.5, 1.0, 2.0):
r = wire_resistance(rho_copper, 10.0, d_mm / 1000.0)
print(f"d = {d_mm} mm, 10 m: R = {r:.3f} ohm")Running this prints about 0.856 Ω for 0.5 mm, 0.214 Ω for 1.0 mm, and 0.053 Ω for 2.0 mm. Each doubling of diameter divides R by 4.
Resistivity versus conductivity
Conductivity (σ, sigma) is the reciprocal of resistivity: σ = 1/ρ, measured in siemens per metre (S/m). Some references tabulate conductivity, especially for metals and for solutions such as seawater. The geometry formula then becomes R = L / (σ · A). Both forms say the same thing. Pick whichever matches the data you have, and do not mix them in one calculation.
Resistivity is not the same as resistance
Keep these two quantities separate:
| Quantity | Symbol | Unit | Depends on |
|---|---|---|---|
| Resistance | R | Ω | Material and shape |
| Resistivity | ρ | Ω·m | Material (and temperature) only |
If you cut a wire in half, each half has half the resistance but the same resistivity. If you stretch a wire to twice its length while its volume stays constant, the area halves. Length doubles and area halves, so R rises by a factor of 4, not 2.
Sheet resistance for thin films
Printed circuit board traces and thin films on chips have a known thickness t. For these, engineers often use sheet resistance, Rs = ρ / t, with units of ohms per square (written Ω/□). A trace of length L and width W then has:
R = Rs · (L / W)
The ratio L/W counts how many squares fit along the trace. A square of any size has the same resistance, because making it larger increases the length and the width in the same proportion. This is a useful shortcut when you lay out resistive tracks and don't want to compute areas.
Temperature and non-uniform conductors
The formula uses ρ at one temperature. Metal resistivity rises with temperature, so a wire carrying heavy current has a higher resistance than the cold value you calculated. A later chapter covers the temperature model in detail. For now, treat tabulated ρ as valid near 20 °C.
R = ρL/A also assumes uniformity:
- The cross-section must be constant along the length.
- The current must spread evenly across the cross-section.
At very high frequencies, current crowds toward the surface of a conductor (the skin effect), and the effective area shrinks. For direct current and low-frequency work the simple formula is accurate. For a tapered or stepped conductor, split it into uniform segments and add their resistances in series.
Common errors
- Wrong area units. Using 1 for a 1 mm² area instead of 1 × 10⁻⁶ m² gives an answer a million times too large.
- Using the diameter as the area. The formula needs the area. Compute π d² / 4 first.
- Using the diameter where the radius is required. If you write π r², use half the diameter.
- Forgetting the return path. In a two-wire circuit the current travels the length twice.
- Mixing ρ and σ. Resistivity goes in the numerator of the formula, conductivity in the denominator.
- Assuming resistance stays constant when stretched. A stretched wire gets both longer and thinner.
Summary of the working model
- R = ρL/A applies to a uniform conductor with current along its length.
- ρ is a property of the material and temperature. R is a property of the specific object.
- R scales linearly with L and inversely with A, so diameter changes act through the square.
- Convert all lengths to metres and areas to square metres before you calculate.
Exercise
A 50 m run of round copper wire has a diameter of 1.0 mm. Using ρ = 1.68 × 10⁻⁸ Ω·m, find its resistance. Then find the voltage drop when it carries 2 A.
Show answer
Area A = π d² / 4 = π × (1.0 × 10⁻³)² / 4 ≈ 7.85 × 10⁻⁷ m². Resistance R = ρL/A = (1.68 × 10⁻⁸ × 50) / 7.85 × 10⁻⁷ ≈ 1.07 Ω. Voltage drop = I × R = 2 × 1.07 ≈ 2.14 V.
Exercise
A uniform wire has resistance 8 Ω. It is drawn out (stretched) until it is twice as long, with its volume unchanged and its resistivity unchanged. What is the new resistance?
Show answer
Volume V = A × L stays constant, so doubling L halves A. R = ρL/A, so R scales with L/A. The new ratio is 2L / (A/2) = 4 L/A. The new resistance is 4 × 8 Ω = 32 Ω.
Exercise
A PCB trace is 40 mm long and 0.25 mm wide. The copper layer has a sheet resistance of 0.5 mΩ per square. What is the trace resistance?
Show answer
The number of squares is L/W = 40 / 0.25 = 160. R = Rs × 160 = 0.5 mΩ × 160 = 80 mΩ, or 0.08 Ω.