Sub topic 9
Resistivity, length, and cross-section
This chapter assumes you can rearrange algebraic equations, use SI prefixes, and apply V = IR. You should also know that resistance is a measure of how strongly a component opposes current.
Resistance depends on the wire, not only the circuit
Ohm's law relates voltage and current. It does not say why a given piece of wire has the resistance it has. That value comes from the material and the shape of the conductor.
For a uniform conductor with constant cross-section:
R = ρ · L / A
- R is resistance in ohms (Ω).
- ρ (rho) is the resistivity of the material in ohm-metres (Ω·m).
- L is the length along the current path in metres.
- A is the cross-sectional area in square metres.
Resistivity belongs to the material. Resistance belongs to a particular piece of that material.
What each factor does
- Length: Doubling L doubles R. Charge must pass through twice as much material.
- Area: Doubling A halves R. A thicker conductor gives the current more parallel paths.
- Material: A larger ρ means more resistance for the same shape.
Typical resistivities
The values below are approximate, at about 20 °C.
| Material | Resistivity ρ (Ω·m) | Role |
|---|---|---|
| Silver | 1.6 × 10⁻⁸ | Best common conductor |
| Copper | 1.68 × 10⁻⁸ | Wiring |
| Aluminium | 2.8 × 10⁻⁸ | Power lines |
| Nichrome | 1.1 × 10⁻⁶ | Heating elements |
| Silicon (pure) | about 640 | Semiconductor |
| Glass | 10¹⁰ to 10¹⁴ | Insulator |
Resistivities span more than twenty orders of magnitude. That range is why the same equation covers both a copper wire and a glass insulator.
Worked example: copper wire
Find the resistance of 1 m of copper wire with a cross-section of 1 mm².
First convert the area to SI units: 1 mm² = 1 × 10⁻⁶ m². Then substitute.
rho_copper = 1.68e-8 # ohm-metres, approximate value at 20 C
length = 1.0 # metres
area = 1.0e-6 # square metres (1 mm^2)
R = rho_copper * length / area
print(f"R = {R:.4f} ohm") # about 0.0168 ohmThe result is about 0.017 Ω. A 50 m run of the same wire is about 0.84 Ω. At 10 A, that run drops V = IR = 8.4 V and dissipates P = I²R = 84 W as heat. For this reason long, high-current runs need thicker wire.
Common errors
- Forgetting that area is squared. 1 mm² is 10⁻⁶ m², not 10⁻³ m². Converting the diameter or area incorrectly is the most frequent mistake.
- Using diameter as area. For a round wire, A = π d² / 4, or π r².
- Counting the round trip wrongly. In a two-wire circuit, current travels out and back. The L in the equation is the total conductor length, so a 50 m cable run has 100 m of wire.
- Treating ρ as fixed. Resistivity changes with temperature, which a later chapter covers. Quoted values assume about 20 °C.
Resistivity and conductance
The reciprocal of resistivity is conductivity, σ = 1/ρ, in siemens per metre. The reciprocal of resistance is conductance, G = 1/R. Some tables list conductivity instead of resistivity. Invert the value before you use R = ρL/A.
Exercise
A round aluminium wire (ρ ≈ 2.8 × 10⁻⁸ Ω·m) has a diameter of 2.0 mm and a length of 100 m. What is its resistance?
Show answer
The area is A = π d² / 4 = π (2.0 × 10⁻³)² / 4 ≈ 3.14 × 10⁻⁶ m². Then R = ρL/A = (2.8 × 10⁻⁸ × 100) / (3.14 × 10⁻⁶) ≈ 0.89 Ω.
Exercise
A wire has resistance 2.0 Ω. It is drawn out until it is twice as long, with its volume unchanged. What is its new resistance?
Show answer
Constant volume means the area halves when the length doubles. R scales as L/A, so it grows by a factor of 2 × 2 = 4. The new resistance is 8.0 Ω.