The transformer and power transmission
This chapter assumes you know Faraday's law, mutual inductance, and rms values of AC. A transformer changes an AC voltage from one value to another. It works only with AC, because it relies on a changing flux.
How a transformer works
A transformer has two coils wound on a shared soft-iron core. The primary coil (Np turns) connects to the AC source. The secondary coil (Ns turns) connects to the load.
The alternating primary current sets up a changing flux in the core. Nearly all of this flux links the secondary, so it induces an emf there. This is mutual inductance in use. With DC, the flux would be constant and the secondary emf would be zero.
The ideal transformer relations
Both coils see the same flux change per turn. For an ideal transformer, which has no losses:
- Voltage ratio: Vs / Vp = Ns / Np
- Current ratio: Is / Ip = Np / Ns
- Power: Vp Ip = Vs Is
If Ns > Np, it is a step-up transformer. The voltage rises and the current falls. If Ns < Np, it is a step-down transformer. A transformer never increases power.
Real transformers and efficiency
Efficiency is η = Pout / Pin = (Vs Is) / (Vp Ip). Real transformers lose energy in four ways:
| Loss | Cause | Remedy |
|---|---|---|
| Copper loss | I²R heating in the windings | Thick wire |
| Eddy current loss | Currents induced in the core | Laminated core |
| Hysteresis loss | Repeated magnetisation reversal | Soft iron core |
| Flux leakage | Some flux misses the secondary | Winding the coils over each other |
Why transmit at high voltage
A line of resistance R carrying current I wastes power I²R as heat. For a fixed power P = VI, raising V lowers I. The loss then falls as 1/V². Stations therefore step the voltage up for transmission and step it down near the consumer.
The next program compares sending 100 kW through a line of 5 Ω at two voltages.
P = 100_000.0 # power to send, in watt
R_line = 5.0 # line resistance, in ohm
for V in (2_000.0, 20_000.0):
I = P / V
loss = I**2 * R_line
print(f"V = {V:.0f} V, I = {I:.1f} A, loss = {loss:.0f} W ({100 * loss / P:.2f}%)")At 2 kV the current is 50 A and the loss is 12 500 W (12.5%). At 20 kV the current is 5 A and the loss is 125 W (0.13%). A tenfold rise in voltage cuts the loss a hundredfold.
Exercise
A step-down transformer has 2000 primary turns and takes 4400 V from the mains. The secondary delivers 220 V at 18 A, and the primary current is 1 A. Find the number of secondary turns and the efficiency.
Show answer
Ns = Np × Vs / Vp = 2000 × 220 / 4400 = 100 turns. Output power = 220 × 18 = 3960 W. Input power = 4400 × 1 = 4400 W. Efficiency = 3960 / 4400 = 0.90, or 90%.