Sub topic 2
Real, Reactive, and Apparent Power
Assume you know Ohm’s law, RMS values, phasors, and the impedance of resistors, inductors, and capacitors. This chapter separates the different kinds of power in a sinusoidal AC circuit.
Real power: the average that does work
Instantaneous power is the product of voltage and current:
p(t) = v(t)i(t)
It changes throughout each AC cycle. The average value is real power, written as P. Real power becomes heat, motion, light, or another useful output.
For RMS voltage V, RMS current I, and phase angle φ between them:
P = VI cos(φ)
Real power is measured in watts (W). The factor cos(φ) is the displacement power factor.
Reactive power: energy exchanged with fields
Inductors store energy in magnetic fields, and capacitors store energy in electric fields. They return this energy to the source during another part of the cycle. This exchange does not produce a net average output.
Reactive power is written as Q:
Q = VI sin(φ)
It is measured in volt-amperes reactive (var).
Q > 0means an inductive, lagging load.Q < 0means a capacitive, leading load.- Pure reactive power has zero real power.
Apparent power: what the source and wiring must carry
Apparent power is the product of RMS voltage and RMS current:
S = VI
It is measured in volt-amperes (VA). It indicates the electrical loading on generators, transformers, conductors, and switches.
For sinusoidal waveforms:
S² = P² + Q²
Thus, a load can require substantial current even when its real power is smaller.
| Quantity | Symbol | Unit | Meaning |
|---|---|---|---|
| Real power | `P` | W | Average power converted to useful output |
| Reactive power | `Q` | var | Energy exchanged with fields |
| Apparent power | `S` | VA | Total voltage-current loading |
The power triangle
The power triangle represents these quantities geometrically. Real power is the horizontal side, reactive power is the vertical side, and apparent power is the hypotenuse.
The power factor is:
power factor = P/S = cos(φ)
For a 230 V load drawing 16.263 A at a 45° lagging angle:
P = 230 × 16.263 × cos(45°) ≈ 2645 WQ = 230 × 16.263 × sin(45°) ≈ 2645 varS = 230 × 16.263 ≈ 3741 VA- Power factor
≈ 0.707, lagging
Exercise
A load has P = 3 kW and Q = 4 kvar. Find its apparent power and power factor.
Show answer
S = √(3² + 4²) = 5 kVA. Power factor = P/S = 3/5 = 0.60. If Q is positive, it is lagging.