Sub topic 3
Power Factor and Why Utilities Care
Assume you know RMS voltage and current, phasors, impedance, and basic trigonometry. Power factor (PF) measures how effectively an AC load turns the current supplied by the source into real power:
PF = P / S
Here, P is real power in watts (W), and S is apparent power in volt-amperes (VA). For sinusoidal voltage and current:
PF = cos(φ)
where φ is the phase angle between voltage and current. A lower PF means more current is needed for the same useful power. This increases losses and voltage drop in generators, transformers, cables, and circuit breakers.
| Quantity | Unit | Meaning |
|---|---|---|
| P | W | Power converted to heat, motion, or other work |
| Q | var | Power exchanged with electric or magnetic fields |
| S | VA | Total RMS power the source and wiring carry |
Leading and Lagging Loads
Inductive loads, such as motors and transformers, draw current after voltage. They have a lagging PF and positive reactive power, Q. Capacitive loads draw current before voltage. They have a leading PF and negative Q.
Complex Power from Phasors
Using RMS phasors, calculate complex power with the conjugate of current:
S = V I*
In rectangular form:
S = P + jQ
The real part is P, the imaginary part is Q, and the magnitude |S| is apparent power. For example, if V = 230 V and I = 10 − 10j A:
S = 230(10 + 10j) = 2300 + j2300 VA
Thus P = 2300 W, Q = 2300 var, and PF is about 0.707 lagging.
Power-Factor Correction
A shunt capacitor supplies negative reactive power locally. For a load with real power P:
Qc = P[tan(cos⁻¹(PFold)) − tan(cos⁻¹(PFnew))]
Then choose the capacitor from:
C = Qc / (2πfV²)
Correction reduces source current, but an oversized capacitor can create leading PF or resonance.
Three-Phase and Distorted Power
For a balanced three-phase system:
P = √3 VL IL PF
where VL and IL are line-to-line voltage and line current. The same PF definition applies.
With distorted waveforms, displacement PF is cos(φ1), based only on the fundamental components. True PF includes harmonics:
True PF = P / (Vrms Irms)
Harmonic current can lower true PF even when displacement PF is near one.
Exercise
A balanced three-phase load uses 400 V line voltage, 10 A line current, and PF = 0.8. What real power does it consume?
Show answer
P = √3 × 400 × 10 × 0.8 ≈ 5.54 kW.