Sub topic 20
The ideal transformer and its losses
This chapter assumes you know Faraday's law, mutual inductance, RMS values and the power factor from the earlier chapters. It also assumes you can read a simple phasor diagram. A transformer is mutual inductance put to practical use. It changes an AC voltage from one value to another while transferring almost all of the power.
The working model
A transformer has two coils wound on a shared soft-iron core. The primary coil (Np turns) connects to the AC source. The secondary coil (Ns turns) connects to the load. The alternating primary current sets up an alternating flux Φ in the core. The core guides almost all of that flux through the secondary as well.
In the ideal case every turn of both coils links the same flux Φ. Faraday's law then gives:
- Primary: ep = −Np dΦ/dt
- Secondary: es = −Ns dΦ/dt
Dividing the two gives the voltage relation:
Vs / Vp = Ns / Np
An ideal transformer is defined by four assumptions:
- The coil resistance is zero.
- There is no flux leakage, so all flux links both coils.
- The core has no eddy-current or hysteresis loss.
- The core permeability is so high that the magnetising current is negligible.
Under these assumptions, input power equals output power:
Vp Ip = Vs Is, so Ip / Is = Ns / Np
| Type | Turns ratio | Voltage | Current |
|---|---|---|---|
| Step-up | N_s > N_p | V_s > V_p | I_s < I_p |
| Step-down | N_s < N_p | V_s < V_p | I_s > I_p |
A step-up transformer raises the voltage and lowers the current. Power is not increased. The transformer works only on changing flux, so DC at the primary gives zero secondary EMF once the current is steady.
Why the primary current depends on the load
With the secondary open, the primary behaves like a nearly pure inductor. It draws a small magnetising current that lags the voltage by about 90°. The average power is close to zero because cos 90° = 0.
When a load is connected, the secondary current I_s produces its own flux. By Lenz's law this flux opposes the core flux. The primary responds by drawing extra current so that the net flux, and therefore the back-EMF, stays fixed. This is how the source "knows" about the load.
The load as seen from the primary is the reflected resistance:
Rin = Vp / Ip = Rload (Np / Ns)²
Worked example
A transformer has Np = 1000 and Ns = 100. It is connected to 220 V and feeds an 11 Ω load. The program below computes the ideal values and then compares transmission at two voltages.
def ideal_transformer(Vp, Np, Ns, R_load):
"""Secondary voltage, secondary current, primary current and power for an ideal transformer."""
Vs = Vp * Ns / Np
Is = Vs / R_load
Ip = Is * Ns / Np
return Vs, Is, Ip, Vp * Ip
print(ideal_transformer(220.0, 1000, 100, 11.0))
# (22.0, 2.0, 0.2, 44.0)
def line_loss(P, V, R_line):
"""Power wasted in a transmission line of resistance R_line when sending P at voltage V."""
I = P / V
return I**2 * R_line
print(line_loss(100_000, 2_000, 5.0)) # 12500.0
print(line_loss(100_000, 20_000, 5.0)) # 125.0The secondary gives 22 V and 2 A, which is 44 W. The primary draws 0.2 A at 220 V, which is also 44 W. The reflected resistance is 11 × 10² = 1100 Ω, and 220 / 1100 = 0.2 A, so the two methods agree.
The line-loss function shows why power is transmitted at high voltage. For fixed power, I = P/V. The loss I²R falls as 1/V². Raising V tenfold cuts the loss a hundredfold. A step-up transformer at the power station and step-down transformers near the consumer make this possible.
Real losses
A real transformer has efficiency η = Pout / Pin, usually 90–99%. Each loss has a cause and a standard remedy.
| Loss | Cause | Remedy |
|---|---|---|
| Copper loss | I²R heating in the windings | Thick wire, low-resistance copper |
| Eddy-current loss | Induced currents circulating in the core | Thin laminations insulated from each other |
| Hysteresis loss | Energy spent each cycle reversing core magnetisation | Soft iron or silicon steel with a narrow B–H loop |
| Flux leakage | Some flux does not link both coils | Wind coils over each other on a closed core |
| Humming | Magnetostriction, where the core flexes at twice the supply frequency | Tight clamping of the core |
Laminations work because they break the eddy-current paths into small loops with high resistance. Eddy-current loss falls without reducing the useful flux.
Common errors
- Using a transformer with a DC source and expecting a steady secondary voltage.
- Writing Vp/Vs = Ns/Np, which inverts the ratio.
- Treating the step-up secondary as delivering more power. Its current is smaller by the same factor.
- Forgetting that the primary current is set by the secondary load. The source does not choose it.
- Using peak values for one side and RMS for the other. Use the same kind on both sides.
Exercise
A step-down transformer reduces 2200 V to 220 V and delivers 4.4 kW to a load. Its efficiency is 80%. Find the primary current, and compare it with the primary current of an ideal transformer.
Show answer
Input power = 4400 / 0.80 = 5500 W. Primary current = 5500 / 2200 = 2.5 A. The ideal transformer would draw 4400 / 2200 = 2 A. The extra 0.5 A supplies the 1100 W lost as heat in the windings and core.
Exercise
An ideal transformer has 400 primary turns on a 220 V supply. The secondary feeds a 55 Ω resistor at 55 V. Find N_s, the secondary current and the primary current.
Show answer
Ns = 400 × 55 / 220 = 100 turns. Is = 55 / 55 = 1 A. Ip = Is × Ns/Np = 1 × 100/400 = 0.25 A. Check the power: 220 × 0.25 = 55 W = 55 × 1 W.